You can name the eCB1 MP+ “
house_connection_eCB1
” to prevent confusing it with
other installed eCB1.
The button “measurement via current transformer” must only be activated when there is a
measuring transformer installed. Press on the button to activate (orange) and deactivate
(grey). Usually (by German law) a measuring transformer is required when the house
connection exceeds 63A.
Charge connector 1
In this case, the eCB1 LR MP+ is responsible for the measurement at the house
connection and does not require a charging point.
Choose „No EVCC“ (EVCC = charge controller).
Press „
proceed
“ to finish the seutup.
Finish setup
Configuration instructions
eCB1
smartmeter
Version: 1.2.3
12