Hansen APP08 Operator Installation & Instruction Manual Download Page 9

9

APP-001b

APR 2007

SYSTEM RESET

 – Resets the system to its pre-star tup 

settings. Actions performed by pressing this key consist of 
clearing any error code(s), clearing air purge log minutes, 
clearing air purge log cycles, clearing water drain log 
minutes, clearing water drain cycles, stopping air and 
water purging processes if active.  The number of purge 
points, the 60 MINUTE AIR PURGE LIMIT setting, and the 
DISPL AY UNITS will not be changed.  

STATUS

 – Pressing this key once displays the total 

time that air has been released in minutes, the number 
of cycles that air has been released, the total time that 
water has been released in minutes, and the number of 
cycles that water has been released.  Pressing this key 
again displays the water concentration in the purger 
evaporator (except the water concentration is not displayed 
during CONCENTRATING WATER mode, because the 
concentration in this mode often exceeds the range of 
the water concentration sensor).  Pressing the key again 
displays the temperature of the evaporator shell, the 
temperature of the liquid inside the purger evaporator, 
and the temperature of the plate heaters (see figure 4).  

Another press of this key displays the pressures in the 

low side and the high side of the purger.  A final press of 
this key returns the display to its normal messages.  If 
this key is not pressed a sufficient number of times to 
return to the normal messages, it will automatically return 
to the normal messages after 2 minutes.

RESET 4444

 – Resets a 4444 alarm condition. See Section 

7, Troubleshooting for an explanation of this alarm. 

OK

 – This key will become active and its LED will illuminate 

when the purger is ready to drain water to the customer 
supplied container.  The display window will also indicate 
READY TO DRAIN. OPEN WATER PURGE SHUT-OFF VALVE 

THEN PRESS “OK” BUTTON.  When the operator opens the 

water purge line shut-off valve and presses this key, the 
purger will drain the accumulated water.  When draining 
is complete, the display window will indicate DRAINING 
IS COMPLETE. CLOSE WATER PURGE SHUT-OFF VALVE 

THEN PRESS “OK” BUTTON.  When the operator closes 

the water purge line shut-off valve and presses this key, 
the LED will turn off and the purger will return to its normal 
mode of collecting air and water.

PURGE POINT ADV.

 –  Press this key to manually advance 

to the next purge point. (This key is not applicable to 
model APPC.)

Summary of Contents for APP08

Page 1: ...RGER Plus is a totally automatic electronically controlled refrigerant noncondensible gas air and water purger for reducing the energy costs of operating an ammonia refrigeration system All models are...

Page 2: ...circumstances only one point is effectively purged The best practice is to purge each condenser and receiver circuit separately It is extremely important to install purge points at locations sure to b...

Page 3: ...some cases a small high pressure auxiliary receiver is located at the outlet of one or more condensers This receiver should have a purge point at the top Where a high pressure float regulator is used...

Page 4: ...ected into the purger The low pressure pumped liquid line feeds makeup liquid as required during purging The line contains liquid ammonia that typically is also contaminated with water which is to be...

Page 5: ...mps electrical supply on a 15 amp circuit breaker are available All models have a 13 mm knockout on the side of the control cabinet to access the power connection terminal strip Any unused knockout ho...

Page 6: ...connecting shut off valves are open See Figure 4 START UP Make sure all piping electrical connections and settings are complete as described in this bulletin Open the foul gas low pressure pumped liq...

Page 7: ...there are no releases to atmosphere 1 WATER BUBBLER WATER BUBBLER OVERFLOW TUBE FOUL GAS LINE LOW PRESSURE PUMPED LIQUID LINE SUCTION LINE FILL LINE D B C FLOW REGULATOR GAUGE VALVE GAUGE VALVE LIQUI...

Page 8: ...system parameters The operator can switch between the two message types by pressing the esc key Control Console Specifications Display Type Character LCD 4 lines by 20 characters w LED backlight Encl...

Page 9: ...and the temperature of the plate heaters see figure 4 Another press of this key displays the pressures in the low side and the high side of the purger A final press of this key returns the display to...

Page 10: ...follows air purge limit 60 minute limit normal 0 60 min startup 1 nolimit purge point enable 01 1 enable 0 skip 02 1 enable 0 skip 03 1 enable 0 skip 04 1 enable 0 skip 05 1 enable 0 skip 06 1 enable...

Page 11: ...normal 7777 loss of lp liq will appear when the liquid make up solenoid valve has been energized for 30 minutes continuously ERROR HEATER FAULT will be displayed if the heaters are on longer than 4 ho...

Page 12: ...1 psid 07 bar check valve in the water purge line to prevent reverse flow of water into the purger from the customer supplied container The water bubbler fill line has a check valve OPERATION OF PURG...

Page 13: ...URGE GAS GAUGE VALVE WIDE OPEN DURING OPERATION CLOSED FOR SERVICING PURGER PURGE GAS 1 32 0 8 MM DIA METERING ORIFICE 0 07 BAR PURGE GAS TO WATER BUBBLER OR TO CUSTOMER SUPPLIED WATER BOTTLE CHECK VA...

Page 14: ...r fill line valve The purger will pump down in several hours To accelerate the process attach ammonia hoses to the oil drain valves and pump out into a suction line Close the low pressure liquid retur...

Page 15: ...por Trap H5600R Relief Valve 300 psi ELECTRICAL 70 1088 Solenoid Coil DIN plug 115V 50 60 Hz 16 Watt 20 2428 Electric Heater 115V 50 60 Hz 750 Watt 20 2477 Electric Heater 230V 50 60 Hz 750 Watt 20 12...

Page 16: ...ctional pushbutton several times until the pressures are displayed Verify that the high side pressure is greater than 80 psig 5 5 barg Action If the high side pressure displayed is less than 80 psig 5...

Page 17: ...id line plugged strainers or the plastic shipping cap still in the liquid line flange Action Inspect piping for a closed shut off valve Open the shut off valves clean the strainer or remove the shippi...

Page 18: ...18 APP 001b APR 2007 THIS PAGE INTENTIONALLY BLANK...

Page 19: ...ce schedule and the Safety Precautions Sheet supplied with this product Escaping refrigerant can cause injury especially to the eyes and lungs WARRANTY All Hansen products except electronics are guara...

Page 20: ...poration 6827 High Grove Boulevard Burr Ridge Illinois 60527 USA Tel 630 325 1565 Fax 630 325 1572 Toll 800 426 7368 Email info hantech com Web www hantech com USA Asia Europe India Latin America Midd...

Reviews: