Hansen APP08 Operator Installation & Instruction Manual Download Page 17

17

APP-001b

APR 2007

CONTROL CONSOLE DISPLAYS 4444

PURGED OVER 60 MINUTE TIME LIMIT. 

If noncondensibles 

are released from the purger for 60 minutes continuously, a 
time delay will close the purge gas solenoid valve (C).  This 

limits the possibility of a substantial amount of refrigerant 
inadvertently being released into the water bubbler in the 
unlikely event of purger malfunction.

R E ASO N  1:

 A large volume of noncondensibles is 

continuously being removed from system.

Action:

 Reset the time delay by pressing the RESET 4444 

functional pushbutton on the Control Console. See 
Figure 5. Delay is now reset for up to another hour of 
continuous purging.  Otherwise, put the purger in New 
System Star t-up mode for continuous purging without 
the 60 minute time limit.

REASON 2:

 Purge gas solenoid valve (C) is not opening 

or the removable seat/orifice is blocked. 

Check:

 Make sure purge gas solenoid valve (C) is energized.  

If not, check for voltage at solenoid coil.

Action:

 Replace the coil if it is burned-out, otherwise 

clean or replace the valve.  See also the Caution section 
on page 19.

REASON 3:

 The shut-off valve located before the purge 

gas solenoid valve (C) is closed.

Check:

  Verify  that  purge  gas  is  not  being  sent  to  the 

bubbler.

Action:

 Open the valve.

CONTROL CONSOLE DISPLAYS 7777

LOSS  OF  LOW-PRESSURE  PUMPED-LIQUID.

    If  the 

liquid line solenoid valve remains energized for more than 

30 minutes, it indicates there is insufficient low-pressure 
pumped-liquid available to maintain an adequate level in 
the flooded evaporator of the purger.  The purger will not 
purge air until this is corrected.

REASON 1:

 Liquid line solenoid valve (B) is not opening 

or the seat/orifice is blocked.

Check:

 Make sure the liquid line solenoid valve (B) is 

energized.    If  not,  check  for  voltage  at  the  solenoid 
coil.

Action:

 Replace the coil if it is burned-out, otherwise 

clean or replace the valve.  See also the Caution section 
on page 19.

REASON 2:

 Liquid line restricted.

Check:

 Look for closed shut-off valves in the pumped-

liquid line, plugged strainers, or the plastic shipping 

cap still in the liquid line flange.

Action:

 Inspect piping for a closed shut-off valve.  Open 

the shut-off valves, clean the strainer, or remove the 
shipping cap.  See also the Caution section on page 

19.

NONCONDENSIBLES ARE NOT BEING 
RELEASED.

(See also page 16; Control Console displays 3333)

REASON 1:

 Noncondensibles not present in system.

Check:

 Compare the refrigerant liquid temperature from 

condenser exit with the condensing pressure. The 
pressure/temperature relationship should be within 2 
or 3 psig (0.14 to 0.21 bar).

Action:

 None at this time.

REASON 2:

 Metering valve plugged.

Symptom:

 The purger appears to be operating properly, 

however, the low-pressure liquid-return line is not 
frosted.

Check:

 Fully open the metering valve to flush out any 

par ticles. Then, close the valve and reopen two turns.

REASON 3:

 “Foul gas” line is flooded with liquid.

Symptom:

 The line from the bottom of the liquid drainer 

often remains frosted.  

Check:

 Inspect condenser and “foul gas” piping.  In many 

cases, the problem is liquid refrigerant being drawn 
from the purge point.  To prevent this from happening, 
select purge point locations above liquid sur faces and 
make sure purge point lines are installed so that only 
vapor, and not liquid, can be drawn in.  Refer to Piping 
Instructions in Section 2 of this bulletin.

Action:

 Correct condenser and “foul gas” piping.

AMMONIA INSTEAD OF NONCONDENSIBLES 

RELEASED FROM PURGER.

REASON 1:

 Purge gas solenoid valve (C) leaking at 

seat.

S y m p to m :

 A slow leak of noncondensibles to the 

bubbler.

Check:

  Look  for  dir t  or  a  worn  seat  in  the  purge  gas 

solenoid valve (C).

Action:

 Remove, clean, or replace the solenoid tube 

plunger or valve.  See also the Caution section on 
page 19.

REASON 2:

 Oil in purger.

Symptom:

 No frost around the low side oil drain valve.

Action:

 Remove oil through both the low side and high 

side  drain  valves  (See  Figure  1)  per  safe  refrigeration 
procedures.  See also the Caution section on page 19.

WATER BUBBLER DEVELOPS EXCESSIVE 

MINERAL COATING.

REASON 1:

 Hard water.

Action: 

Add vinegar to the bubbler water.  Then, clean with 

the supplied brush.  Use a water conditioning housing 
and car tridge in the water supply line to the purger.

Summary of Contents for APP08

Page 1: ...RGER Plus is a totally automatic electronically controlled refrigerant noncondensible gas air and water purger for reducing the energy costs of operating an ammonia refrigeration system All models are...

Page 2: ...circumstances only one point is effectively purged The best practice is to purge each condenser and receiver circuit separately It is extremely important to install purge points at locations sure to b...

Page 3: ...some cases a small high pressure auxiliary receiver is located at the outlet of one or more condensers This receiver should have a purge point at the top Where a high pressure float regulator is used...

Page 4: ...ected into the purger The low pressure pumped liquid line feeds makeup liquid as required during purging The line contains liquid ammonia that typically is also contaminated with water which is to be...

Page 5: ...mps electrical supply on a 15 amp circuit breaker are available All models have a 13 mm knockout on the side of the control cabinet to access the power connection terminal strip Any unused knockout ho...

Page 6: ...connecting shut off valves are open See Figure 4 START UP Make sure all piping electrical connections and settings are complete as described in this bulletin Open the foul gas low pressure pumped liq...

Page 7: ...there are no releases to atmosphere 1 WATER BUBBLER WATER BUBBLER OVERFLOW TUBE FOUL GAS LINE LOW PRESSURE PUMPED LIQUID LINE SUCTION LINE FILL LINE D B C FLOW REGULATOR GAUGE VALVE GAUGE VALVE LIQUI...

Page 8: ...system parameters The operator can switch between the two message types by pressing the esc key Control Console Specifications Display Type Character LCD 4 lines by 20 characters w LED backlight Encl...

Page 9: ...and the temperature of the plate heaters see figure 4 Another press of this key displays the pressures in the low side and the high side of the purger A final press of this key returns the display to...

Page 10: ...follows air purge limit 60 minute limit normal 0 60 min startup 1 nolimit purge point enable 01 1 enable 0 skip 02 1 enable 0 skip 03 1 enable 0 skip 04 1 enable 0 skip 05 1 enable 0 skip 06 1 enable...

Page 11: ...normal 7777 loss of lp liq will appear when the liquid make up solenoid valve has been energized for 30 minutes continuously ERROR HEATER FAULT will be displayed if the heaters are on longer than 4 ho...

Page 12: ...1 psid 07 bar check valve in the water purge line to prevent reverse flow of water into the purger from the customer supplied container The water bubbler fill line has a check valve OPERATION OF PURG...

Page 13: ...URGE GAS GAUGE VALVE WIDE OPEN DURING OPERATION CLOSED FOR SERVICING PURGER PURGE GAS 1 32 0 8 MM DIA METERING ORIFICE 0 07 BAR PURGE GAS TO WATER BUBBLER OR TO CUSTOMER SUPPLIED WATER BOTTLE CHECK VA...

Page 14: ...r fill line valve The purger will pump down in several hours To accelerate the process attach ammonia hoses to the oil drain valves and pump out into a suction line Close the low pressure liquid retur...

Page 15: ...por Trap H5600R Relief Valve 300 psi ELECTRICAL 70 1088 Solenoid Coil DIN plug 115V 50 60 Hz 16 Watt 20 2428 Electric Heater 115V 50 60 Hz 750 Watt 20 2477 Electric Heater 230V 50 60 Hz 750 Watt 20 12...

Page 16: ...ctional pushbutton several times until the pressures are displayed Verify that the high side pressure is greater than 80 psig 5 5 barg Action If the high side pressure displayed is less than 80 psig 5...

Page 17: ...id line plugged strainers or the plastic shipping cap still in the liquid line flange Action Inspect piping for a closed shut off valve Open the shut off valves clean the strainer or remove the shippi...

Page 18: ...18 APP 001b APR 2007 THIS PAGE INTENTIONALLY BLANK...

Page 19: ...ce schedule and the Safety Precautions Sheet supplied with this product Escaping refrigerant can cause injury especially to the eyes and lungs WARRANTY All Hansen products except electronics are guara...

Page 20: ...poration 6827 High Grove Boulevard Burr Ridge Illinois 60527 USA Tel 630 325 1565 Fax 630 325 1572 Toll 800 426 7368 Email info hantech com Web www hantech com USA Asia Europe India Latin America Midd...

Reviews: