background image

Operator Installation 

& Instruction Manual

AUTO-PURGER

®

 PLUS, APP

Non-condensible Gas (Air) &

Water Purger for Ammonia

Bulletin APP-001b

APR 2007

Operator Installation & Instruction 

Manual for Models APP08, APP16, 

APP24 and APPC

AUTO-PURGER

®

 PLUS, APP

SECTION 1   INTRODUCTION

The internal surface area and flooded evaporator efficiency 

gives the AUTO-PURGER Plus two to three times the foul 
gas condensing capacity of an Armstrong Purger and 10 
times the capacity of purgers with small electric hermetic 
compressors. In a system with normal noncondensible 

loads, all models will handle a 750 ton (2600 kW) ammonia 
plant at suction pressures below atmospheric pressure or 

a 1500 ton (5300 kW ) ammonia plant at positive suction 
pressures. The amount of noncondensibles in the system 

is based on many factors including age, maintenance 
practices, and operating temperature.

The number of purgers required for a system depends on 

the number of installed purge points. Twenty-four purge 
points is the maximum practical number per purger. For 
example, a system with 24 points set to purge for 10 
minutes per point requires a 240 minute (4 hour) cycle. 
Each purge point can be purged 6 times a day. This may, or 
may not, be adequate. Therefore, a second purger should 
be used and the purge points divided equally between 
the two purgers.

The AUTO-PURGER Plus can operate over a wide range of 

condensing pressures. This is important for refrigeration 
systems that operate at low condensing pressures during 
cold ambient conditions.

The AUTO-PURGER Plus is a totally automatic, electronically-

controlled refrigerant noncondensible gas (air) and 
water purger for reducing the energy costs of operating 
an ammonia refrigeration system. All models are pre-
assembled, pre-wired, insulated, and include an automatic 
water bubbler, a relief valve, and an isolation service valve 
package. Installation requires piping the foul gas line, low-
pressure pumped-liquid line, low-pressure liquid return 

line, suction line, water bubbler fill and drain lines, relief 

valve vent line, water purge line to a customer supplied 
container, and power connection, and wiring the remote 
purge point solenoid valves. Purge point solenoid valves 
must be purchased separately and must be a minimum 
of ½” (13 mm) por t size.

In addition, a computerized model—APPC—is available 
where a separate plant computer or programmable logic 
controller (PLC) is used to independently operate the 
various remote purge point solenoid valves.

Water contamination in an industrial ammonia refrigeration 
system can lower system efficiency, and increase the 
electrical costs required to run the system’s refrigeration 
compressors.  Ammonia refrigerant that is contaminated 
with water requires a lower suction pressure to maintain 
the same evapor ator temper ature than would pure 
ammonia refrigerant.  The requirement to maintain a 

lower suction pressure than would be necessar y if the 

water contamination were removed is a waste of electrical 
energy.  For water removal, the AUTO-PURGER Plus has 
the following capacities:

  5% system water concentration – 3 gallons of water 

removed per day

  10% system water concentration – 5 gallons of water 

removed per day

  20% or more system water concentration – 7 gallons of 

water removed per day.

Summary of Contents for APP08

Page 1: ...RGER Plus is a totally automatic electronically controlled refrigerant noncondensible gas air and water purger for reducing the energy costs of operating an ammonia refrigeration system All models are...

Page 2: ...circumstances only one point is effectively purged The best practice is to purge each condenser and receiver circuit separately It is extremely important to install purge points at locations sure to b...

Page 3: ...some cases a small high pressure auxiliary receiver is located at the outlet of one or more condensers This receiver should have a purge point at the top Where a high pressure float regulator is used...

Page 4: ...ected into the purger The low pressure pumped liquid line feeds makeup liquid as required during purging The line contains liquid ammonia that typically is also contaminated with water which is to be...

Page 5: ...mps electrical supply on a 15 amp circuit breaker are available All models have a 13 mm knockout on the side of the control cabinet to access the power connection terminal strip Any unused knockout ho...

Page 6: ...connecting shut off valves are open See Figure 4 START UP Make sure all piping electrical connections and settings are complete as described in this bulletin Open the foul gas low pressure pumped liq...

Page 7: ...there are no releases to atmosphere 1 WATER BUBBLER WATER BUBBLER OVERFLOW TUBE FOUL GAS LINE LOW PRESSURE PUMPED LIQUID LINE SUCTION LINE FILL LINE D B C FLOW REGULATOR GAUGE VALVE GAUGE VALVE LIQUI...

Page 8: ...system parameters The operator can switch between the two message types by pressing the esc key Control Console Specifications Display Type Character LCD 4 lines by 20 characters w LED backlight Encl...

Page 9: ...and the temperature of the plate heaters see figure 4 Another press of this key displays the pressures in the low side and the high side of the purger A final press of this key returns the display to...

Page 10: ...follows air purge limit 60 minute limit normal 0 60 min startup 1 nolimit purge point enable 01 1 enable 0 skip 02 1 enable 0 skip 03 1 enable 0 skip 04 1 enable 0 skip 05 1 enable 0 skip 06 1 enable...

Page 11: ...normal 7777 loss of lp liq will appear when the liquid make up solenoid valve has been energized for 30 minutes continuously ERROR HEATER FAULT will be displayed if the heaters are on longer than 4 ho...

Page 12: ...1 psid 07 bar check valve in the water purge line to prevent reverse flow of water into the purger from the customer supplied container The water bubbler fill line has a check valve OPERATION OF PURG...

Page 13: ...URGE GAS GAUGE VALVE WIDE OPEN DURING OPERATION CLOSED FOR SERVICING PURGER PURGE GAS 1 32 0 8 MM DIA METERING ORIFICE 0 07 BAR PURGE GAS TO WATER BUBBLER OR TO CUSTOMER SUPPLIED WATER BOTTLE CHECK VA...

Page 14: ...r fill line valve The purger will pump down in several hours To accelerate the process attach ammonia hoses to the oil drain valves and pump out into a suction line Close the low pressure liquid retur...

Page 15: ...por Trap H5600R Relief Valve 300 psi ELECTRICAL 70 1088 Solenoid Coil DIN plug 115V 50 60 Hz 16 Watt 20 2428 Electric Heater 115V 50 60 Hz 750 Watt 20 2477 Electric Heater 230V 50 60 Hz 750 Watt 20 12...

Page 16: ...ctional pushbutton several times until the pressures are displayed Verify that the high side pressure is greater than 80 psig 5 5 barg Action If the high side pressure displayed is less than 80 psig 5...

Page 17: ...id line plugged strainers or the plastic shipping cap still in the liquid line flange Action Inspect piping for a closed shut off valve Open the shut off valves clean the strainer or remove the shippi...

Page 18: ...18 APP 001b APR 2007 THIS PAGE INTENTIONALLY BLANK...

Page 19: ...ce schedule and the Safety Precautions Sheet supplied with this product Escaping refrigerant can cause injury especially to the eyes and lungs WARRANTY All Hansen products except electronics are guara...

Page 20: ...poration 6827 High Grove Boulevard Burr Ridge Illinois 60527 USA Tel 630 325 1565 Fax 630 325 1572 Toll 800 426 7368 Email info hantech com Web www hantech com USA Asia Europe India Latin America Midd...

Reviews:

Related manuals for APP08