1
Turn off Ln2 feed
2
Turn power ON to chamber
3
Open top cover of Proximity Valve Positioner
4
Press and Hold Enter Key Until AUTO CAL shown on
display
5
Press Up until you get to VALVE onscreen Press Enter
6
Press Down until you find USER SET on Screen Press
Enter
Adjustment of User Characteristics (USER SET)
1. Push <ENTER> at VALVE mode and ACT RA or ACT DA is
displayed.
2. Push <DOWN> twice, then USER SET mode is started.
3. Push <ENTER>. *P0 SET mode is displayed. In this mode, users
can adjust the first point of characteristic in 16 points. The number
on the LCD is the valve stroke percentage set to P0.
4. Adjust valve stroke percentage using <UP> or <DOWN>.
5. Save it with <ENTER>. While P0 value is being saved, *P1 SET
mode is displayed.
6. *P1 SET mode is used to adjust the second point of characteristic in
16 points. Adjustment method is the same as *P0 SET mode.
7. Save the valve stroke percentage from P2 to P15 in the same way.
8. After adjustment of valve stroke percentage at *P15 SET mode, save
it with <ENTER>.
9. +SER SET is displayed. Sixteen points of valve stroke percentage
are all set. Push <ESC> three times to return to RUN mode.
Adjustment of Tight Shut Open (TSHUT OP)
1.
Push <ENTER> at VALVE mode and ACT RA or ACT DA is
displayed. Push <DOWN> three times at this mode. TSHUT OP is
displayed.
2.
Push <ENTER>. *SHUT OP mode is displayed and in this mode
users can set stroke at the time of Tight Open. Initial setting is done
as 100%, which means cancellation of this function. Adjust the
value (ex: 95.0%) by pushing <UP> or <DOWN> and save it with
<ENTER>. +SHUT OP is displayed.
3.
Push <ESC> three times to return to RUN mode.
Adjustment of Tight Shut Close (TSHUT CL)
1. Push <ENTER> at VALVE mode and ACT RA or ACT DA is
displayed. Push <DOWN> four times at this mode. TSHUT CL is
displayed.
2. Push <ENTER>. *SHUT CL mode is displayed and in this mode
users can set stroke at the time of Tight Close. Initial setting is done
as 0.3%. 0% means cancellation of this function. Adjust the value
(ex: 0.5%) by pushing <UP> or <DOWN> and save it by pushing
<ENTER>. +SHUT CL is displayed.
3. Push <ESC> three times to return to RUN mode.
Adjustment of Split Range (SPLIT)
1.
Push <ENTER> at VALVE mode and ACT RA or ACT DA is
displayed.
2.
Push <DOWN> five times and SPLIT mode is displayed. The
numbers on the LCD are the range of current signal input to the
positioner. 4 to 20 mA current signal is set as the standard.
3.
Push <ENTER>. *SPLIT mode is displayed and input signal range
can be adjusted. Adjust input signal range with <UP> or <DOWN>
and save it with <ENTER>.
4.
+SPLIT mode is displayed while saving adjusted range. Push
<ESC> three times to return to RUN mode.
VIEW Mode
This mode provides users with various information about the Series v275
positioners. In this mode, users can change the valve stroke types
displayed on LCD to % or numbers. Refer to the next table for
information and description displayed on VIEW mode.
1.
Push <DOWN> at AUTO CAL mode and VIEW mode is displayed.
2.
Push <ENTER> at VIEW mode, then information mode is started.
3.
Check information by using <UP> or <DOWN> and push <ESC>.
4.
Push <ESC> again to return to RUN mode.
page 9
(1) Push <ENTER>.
(2) Push <DOWN> twice.
(3) Push <ENTER>.
(4) Adjust with <UP>,
<DOWN>.
(5) Push <ENTER>.
(6) Set P1.
(7) Set P2-P15.
(8) Push <ENTER>.
(9) Push <ESC>
three times.
RUN
MODE.
(1) Push <DOWN>
three times.
(2) Push <ENTER>.
(3)
Push <ENTER>
after adjustment with
<UP>, <DOWN>.
(4) Push <ESC>
three times.
RUN
MODE.
(1) Push <DOWN>
four times.
(2) Push <ENTER>.
(3)
Push <ENTER>
after adjustment with
<UP>, <DOWN>.
(4) Push <ESC>
three times.
RUN
MODE.
(1) Push <ENTER>.
(2) Push <DOWN>
five times.
(3)
Push <ENTER>.
(4)
Push <ENTER>
after adjustment with
<UP>, <DOWN>.
(5)
Push <ESC>
three times.
RUN
MODE.
(1) Push <DOWN>
four times.
(2) Push <ENTER>.
(3)
Check data with
<UP>, <DOWN>.
(4)
Push <ESC>.
RUN
MODE.
Authorization and Copyright of this document is
controlled by Hanse Environmental Inc.
51
Summary of Contents for VTC Series
Page 1: ...Operation and Maintenance Instructions for Hanse Environmental Inc VTC Series Rev H 2018 ...
Page 42: ...Authorization and Copyright of this document is controlled by Hanse Environmental Inc 42 ...
Page 56: ...Authorization and Copyright of this document is controlled by Hanse Environmental Inc 56 ...
Page 57: ...Authorization and Copyright of this document is controlled by Hanse Environmental Inc 57 ...
Page 58: ...Authorization and Copyright of this document is controlled by Hanse Environmental Inc 58 ...
Page 59: ...Authorization and Copyright of this document is controlled by Hanse Environmental Inc 59 ...
Page 60: ...Authorization and Copyright of this document is controlled by Hanse Environmental Inc 60 ...
Page 61: ...Authorization and Copyright of this document is controlled by Hanse Environmental Inc 61 ...
Page 64: ...Authorization and Copyright of this document is controlled by Hanse Environmental Inc 64 ...
Page 65: ...Authorization and Copyright of this document is controlled by Hanse Environmental Inc 65 ...
Page 66: ...Authorization and Copyright of this document is controlled by Hanse Environmental Inc 66 ...
Page 69: ...Authorization and Copyright of this document is controlled by Hanse Environmental Inc 69 ...
Page 70: ...Authorization and Copyright of this document is controlled by Hanse Environmental Inc 70 ...
Page 71: ...Authorization and Copyright of this document is controlled by Hanse Environmental Inc 71 ...
Page 79: ...Authorization and Copyright of this document is controlled by Hanse Environmental Inc 79 ...
Page 83: ...Authorization and Copyright of this document is controlled by Hanse Environmental Inc 83 ...