3.
Enter 0.000V from the voltage source to the controller. Allow at least 10 seconds
to stabilize. Press right arrow once at the Calibrate Input 2 prompt. At the
0.000V prompt press right arrow once and to store the 0.000V input press up
arrow once.
4.
Enter 10.000V from the voltage source to the controller. Allow at least 10
seconds to stabilize. Press right arrow once at the Calibrate Input 2 prompt
(Factory Page). At the 10.000V prompt press right arrow once and to store the
10.000V input press up arrow once.
Input 3 Thermocouple Input Procedure
Equipment
•
Type J reference compensator with reference junction at 32°F (0°C), or type J
thermocouple calibrator to 32°F (0°C).
•
Precision millivolt source, 0 to 50mV minimum range, 0.002mV resolution.
Setup and Calibration
1.
Connect the correct power supply to terminals 1, 2 and 3 (see the Wiring
Chapter and the Appendix).
2.
Connect the millivolt source to Input 3 terminals 56 (-) and 55 (+).
3.
Enter 50.000mV from the millivolt source. Allow at least 10 seconds to stabilize.
Press the Right Key once at the Calibrate Input 3 prompt (Factory Page). At the
50.00mV prompt press Right Key once and to store 50.00mV press the Up Key
once.
4.
Enter 0.000mV from the millivolt source. Allow at least 10 seconds to stabilize.
At the 0.00mV prompt press Right Key once and to store 0.00mV press Up Key
once.
5.
Disconnect the millivolt source and connect the reference compensator or
thermocouple calibrator to Input 3 terminals 56 (-) and 55 (+). With type J
thermocouple wire, if using a compensator turn it on and short the input wires.
When using a type J calibrator, set it to simulate 32°F (0°C). Allow 10 seconds
for the controller to stabilize. Press Right Key once at the Calibrate Input x (1 or
2) prompt (Factory Page). At the 32°F Type J prompt press Right Key once and
to store type J thermocouple calibration press Up Key once.
6.
Rewire for operation and verify calibration.
Output 1A Milliamperes (Not Required)
Equipment
•
Precision volt/ammeter with 3.5-digit resolution.
Setup and Calibration
1.
Connect the correct power supply to terminals 1, 2 and 3 (see the Wiring
Chapter and the Appendix).
2.
Connect the volt/ammeter to terminals 42 (+) and 43 (-).
3.
Press the Right Key at the Calibrate Output 1A prompt. At the 4.000mA prompt
press Right Key once. Use the Up Key or the Down Key to adjust the display to
the reading on the volt/ammeter. The controller should stabilize within one
second. Repeat until the volt/ammeter reads 4.000mA. Press Right Key to store
the value.
Authorization and Copyright of this document is
controlled by Hanse Environmental Inc.
24
Summary of Contents for VTC Series
Page 1: ...Operation and Maintenance Instructions for Hanse Environmental Inc VTC Series Rev H 2018 ...
Page 42: ...Authorization and Copyright of this document is controlled by Hanse Environmental Inc 42 ...
Page 56: ...Authorization and Copyright of this document is controlled by Hanse Environmental Inc 56 ...
Page 57: ...Authorization and Copyright of this document is controlled by Hanse Environmental Inc 57 ...
Page 58: ...Authorization and Copyright of this document is controlled by Hanse Environmental Inc 58 ...
Page 59: ...Authorization and Copyright of this document is controlled by Hanse Environmental Inc 59 ...
Page 60: ...Authorization and Copyright of this document is controlled by Hanse Environmental Inc 60 ...
Page 61: ...Authorization and Copyright of this document is controlled by Hanse Environmental Inc 61 ...
Page 64: ...Authorization and Copyright of this document is controlled by Hanse Environmental Inc 64 ...
Page 65: ...Authorization and Copyright of this document is controlled by Hanse Environmental Inc 65 ...
Page 66: ...Authorization and Copyright of this document is controlled by Hanse Environmental Inc 66 ...
Page 69: ...Authorization and Copyright of this document is controlled by Hanse Environmental Inc 69 ...
Page 70: ...Authorization and Copyright of this document is controlled by Hanse Environmental Inc 70 ...
Page 71: ...Authorization and Copyright of this document is controlled by Hanse Environmental Inc 71 ...
Page 79: ...Authorization and Copyright of this document is controlled by Hanse Environmental Inc 79 ...
Page 83: ...Authorization and Copyright of this document is controlled by Hanse Environmental Inc 83 ...