36
Liquid injection applied with high temperature expansion valve
Select the high temperature expansion valve, which can sense the discharge temperature with its remote bulb. This
can control the opening of expansion valve proportionally, and can reach the best cooling effect; it will control the
compressor discharge temperature at an optimal situation of around 80
°
C.
It can also be installed with an additional solenoid valve or service valve in front of the high temperature expansion
valve for the maintenance purposes. The solenoid valve will be opened while starting the compressor. The equilibrium
tube of high temperature expansion valve should be connected to the high-pressure side to counter the internal
pressure.
However, when additional cooling in compression chamber like economizer operation, oil cooler application is used, or
when condensing temperature is low, discharge temperature may be kept low and liquid injection may not be turned on,
although motor load is severe and motor coil temperature is high. This may lead to motor failure. Therefore, in
applications mentioned above, Pt100 or Pt1000 for liquid injection to motor is recommended instead.
Figure 7.3: Liquid injection (high temperature type) Figure 7.4: Liquid injection (high temperature type)
connected to motor to compression chamber
b. Oil cooler applications
Compared to liquid injection applications, external oil cooler application reduces the discharge temperature and at the
same time gives better efficiency. Oil cooler application can be classified into 3 types: cooling by refrigerant, cooling by
ambient air, cooling by cooling water. Oil cooler capacity can be calculated manually or using HANBELL selection
software. When calculating
manually, worst case operating conditions must be considered: minimum evaporating
temperature, maximum suction gas superheat, maximum condensing temperature and the operation mode.
Cooling by refrigerant
The cooler uses refrigerant as the cooling medium. A basic
refrigerant-cooled oil cooling system is shown in Figure 7.5.
Figure 7.5: Oil cooling by refrigerant
In the oil cooler, solenoid
valve for refrigerant circuit
is controlled by oil
temperature of the oil outlet
of compressor.
Summary of Contents for RC2-AVI Series
Page 13: ...12 4 3 Compressor outline SI mm Imperial in UNIT...
Page 14: ...13 UNIT SI mm Imperial in...
Page 15: ...14...
Page 16: ...15...
Page 17: ...16 SI mm Imperial in UNIT...
Page 18: ...17...