25
RC2-1020AVI, RC2-1270AVI cable box
Figure 4.16: IP54 cable box
i. Liquid injection system (solenoid valve + expansion valve)
Liquid injection system is an auxiliary mechanism to cool motor coil. RC2-AVI series’ motor is cooled by suction return
gas. In high-condensing-temperature or low-evaporating-temperature applications, liquid injection system is
recommended to cool motor coil auxiliary. In high-compression-ratio applications, liquid injection to compression
chamber is also recommended to absorb high compression heat due to high compression ratio to maintain normal
discharge temperature. Please refer to Chapter 7 for details of additional cooling.
Hanbell provides the following liquid injection expansion valves and solenoid valves for customers’ options. Please
refer to capacity recommended in Hanbell selection software to choose appropriate liquid injection expansion valves.
Brand
Model
Low Temp.
Type
High Temp.
Type
SPORLAN
Y1037-FV-3-180,3/8"SAE
○
Y1037-FV-5-180,3/8"SAE
○
ALCO
TCLE-3HW-6A
○
TCLE-5HW-6A
○
TCLE-10HW-6A
○
FUJIKOKI
JBE-E60HFKT-1
○
j. Liquid injection system (solenoid valve + stop valve)
This simple liquid injection system adjusts amount of
liquid injection by stop valve, suitable for application
with level load and ambient temperature but it’s not
recommended. Opening ratio of stop valve could not
vary with system loading and change of temperatures.
Therefore, frequent check of discharge temperature
can prevent damage of compressor due to over cooling
or insufficient cooling.
k. External oil separator
For improvement of oil return in flooded-type, low-temperature and parallel systems, system with long piping, Hanbell
specially designs a complete series of external oil separators – OS series with characteristics of high separation
efficiency and low pressure drop. The following table shows details of OS series:
Note: It is recommended to install a muffler before the external oil separator to avoid noise and vibration caused by
resonance.
(
) Technical data
Ⅰ
:
Model
Type
Oil Volume (Liter)
Range of application based on
Displacement (m
3
/hr)
(Recommended)
Shell Diameter
High level
Low level
OS40
Vertical
17
9
205
14”
OS50
Vertical
22
12
206~270
16”
OS65
Vertical
31
18
271~440
18”
OS80
Horizontal
33
20
441~705
20”
OS100
Horizontal
40
27
706~1120
20”