PROBLEMS 

POSSIBLE CAUSES 

REMEDY / CORRECTIVE ACTION 

Abnormal vibration and 

noise of compressor 

Liquid compression 

Adjust proper suction superheat 

Friction  between  rotors  or  between  rotor  and 

compression chamber 

Change screw rotors or compression chamber or both. 

Insufficient lubrication oil 

Check the oil supply of the compressor is enough, add some 

oil if necessary 

Loose internal parts 

Dismantle the compressor and tighten/change loose parts 

System  harmonic  vibration  caused  by  improper  piping 

system 

Check the system piping and if possible replace steel pipe by 

copper pipe 

External debris fallen into the compressor 

Dismantle the compressor and check the damage. Clean and 

polish  rotor  and  chamber  surfaces.  Replacement  might  be 

needed depending on damages. 

Friction between slide valve and rotors 

Dismantle the compressor and change damaged parts 

Motor rotor rotates imbalance 

Check and repair 

Motor line open 

Check 

Start-up difficulties 

Tripped overload 

Check the electrical connection 

Screw rotors seized 

Replace screw rotors, bearings etc… 

Broken motor 

Change motor 

Insufficient refrigerant 

Leakage  test.  Charge  additional  refrigerant  and  adjust 

suction superheat less than 10K 

High discharge temperature 

Poor heat exchange in condenser 

Check and clean the condenser 

Refrigerant overcharge 

Reduce the refrigerant charge 

Air/moisture in refrigerant system 

Recover, purify refrigerant and vacuum system 

Improper expansion valve 

Check and adjust proper suction super heat 

Insufficient lubrication oil 

Check the oil level and add oil 

Damaged bearings 

Stop  the  compressor  and  change  the  bearings  and  other 

necessary parts 

Improper Vi value 

Change the slide valve 

No  system  additional  cooling  (Liquid  injection  or  oil 

cooler) 

Install additional system cooling (liquid injection or oil cooling 

or both base on working condition limitation) 

Lack of refrigerant 

Check for leaks. Charge additional refrigerant 

Compressor losses oil 

Improper system piping 

Check and correct the piping or install an external oil 

separator 

Liquid fills back 

Maintain suitable suction superheat at compressor 

Lack of refrigerant 

Check for leakage. Charge additional refrigerant 

Low suction pressure 

Evaporator dirty or iced 

Defrost or clean coil 

Clogged liquid line filter drier 

Replace the cartridge 

Clogged suction line or compressor suction strainer 

Clean or change suction strainer 

Expansion valve malfunctioning 

Check and reset for proper superheat 

Condensing temperature too low 

Check means for regulating condensing temperature 

Note: Replacements of compressor parts should be performed by a qualified / certified serviceman with full knowledge 

of HANBELL screw compressors or HANBELL service engineers.

 

 

Summary of Contents for RC2-AV Series

Page 1: ...ge 11 4 Compressor lifting and installation 12 4 1 Compressor lifting 12 4 2 Mounting the compressor 12 4 3 RC2 AV series compressor outline drawings 14 4 4 Compressors accessories 37 5 Electrical dat...

Page 2: ...rolled under severe quality procedures and good service to all customers RC2 AV series compressor is equipped with liquid injection economizer connection PTC motor temperature thermistors discharge te...

Page 3: ...s and description of design 2 1 Compressor nomenclature RC 2 x x x x A V V for applications with variable frequency driver Refrigerant Code A R134a R1234ze Compressor Displacement at 50Hz m 3 hr RC mo...

Page 4: ...6 1750 3550 84 70 16 610 RC2 410AV 407 1750 4750 125 78 16 730 RC2 430AV 423 1750 4750 125 78 16 735 RC2 470AV 471 1750 4750 144 90 18 800 RC2 510AV 508 1750 3550 117 98 20 760 RC2 550AV 549 1750 4750...

Page 5: ...able box RC2 200AV RC2 230AV RC2 260AV RC2 300AV RC2 310AV RC2 340AV RC2 370AV RC2 410AV RC2 430AV RC2 470AV RC2 510AV RC2 580AV construction 1 2 3 4 5 6 7 8 9 14 15 16 17 18 19 20 21 22 23 24 25 26 2...

Page 6: ...8 Oil separator baffle 16 Vi plug key 24 Oil guiding ring RC2 710AV RC2 790AV RC2 830AV RC2 930AV Construction Figure 4 Item Description Item Description Item Description Item Description 1 Compresso...

Page 7: ...discharge ends as well as angular contact ball bearings i e axial bearings at discharge end A three phase two pole squirrel cage induction motor drives the compressor The motor rotor is located on the...

Page 8: ...as is trapped inside the interlobe space b Compression As the male rotor and female rotor meshes the interlobe space moves towards to discharge end and its volume decreases so that gas pressure increa...

Page 9: ...ing for signals connected to VFD should be isolated from wirings of VFD power supply at a distance 3 PLC microcontroller and VFD should be well grounded respectively to prevent cross interference Proc...

Page 10: ...will rise simultaneously In order to keep compressor running safely and continuously Hanbell recommends the following additional cooling devices 1 Oil cooler or 2 Liquid injection to chamber or 3 Liq...

Page 11: ...icant flow to bearings While reverse running it is unable to see the oil flow via sight glass The normal oil level in the compressor oil sump should be maintained above the top of the low level sight...

Page 12: ...d then change oil every 20 000 hours or after 3 years continuous running while the system operates in good condition 2 Avoid clogging in oil filter with debris or swarf which may cause bearing failure...

Page 13: ...ins or steel cables Figure 9 Lifting the compressor with safety ropes 4 2 Mounting the compressor The installation of the compressor in the refrigeration system should be made accessible and make sure...

Page 14: ...ischarge piping to minimize vibration and noise 3 Remove oxidized impurities swarf or debris brought by welding in the piping tubes If they fall into the compressor the oil filter might be clogged res...

Page 15: ...4 3 RC2 AV series compressor outline drawings...

Page 16: ...15...

Page 17: ...16 UNIT SI mm Imperial in...

Page 18: ...17...

Page 19: ...18...

Page 20: ...19...

Page 21: ...20...

Page 22: ...21...

Page 23: ...22...

Page 24: ...23...

Page 25: ...24...

Page 26: ...25...

Page 27: ...26...

Page 28: ...27...

Page 29: ...28...

Page 30: ...29...

Page 31: ...30...

Page 32: ...31...

Page 33: ...32...

Page 34: ...33 SI mm Imperial in UNIT...

Page 35: ...34...

Page 36: ...35...

Page 37: ...36...

Page 38: ...evel switch Oil drain valve Liquid injection system solenoid valve expansion valve Liquid injection system solenoid valve stop valve Horizontal check valve External oil separator External oil filter O...

Page 39: ...D E F G H I 2 102 6 53 69 91 65 90 85 5 2 1 2 122 6 69 89 111 85 110 97 5 3 138 6 80 99 121 95 120 108 5 4 163 6 96 124 146 120 145 123 5 Figure 12 Suction check valve outline drawing Horizontal type...

Page 40: ...97 6 3 138 4 95 99 121 80 100 120 108 6 4 163 4 120 124 146 96 125 145 123 6 6 238 5 190 195 216 146 190 215 160 6 No 1 2 3 4 5 6 7 8 Item Body C clipper Spring Valve platet Gasket Nut Guide seat Shaf...

Page 41: ...2 90 Suction Copper 3 1 8 76 145 50 79 8 90 3 5 8 92 4 103 4 1 8 105 1 116 Steel 3 90 2 105 3 1 2 102 8 117 4 115 6 128 RC2 510 RC2 550 RC2 580 Discharge Copper 2 1 8 66 120 45 54 3 65 2 5 8 67 77 3 1...

Page 42: ...75 256 115 18 105 M16x2 105 2 70 90 60 69 91 6 5 122 86 280 128 18 120 M16x2 120 2 1 2 90 110 67 89 111 6 5 137 95 307 153 18 140 M16x2 140 3 100 120 80 99 121 6 5 154 117 398 177 22 160 M20x2 5 160 4...

Page 43: ...frequency drive application Technical data of INT69HBY Supply voltage AC 50 60 Hz 115 120V 15 10 3VA AC 50 60 Hz 230 240V 15 10 3VA Ambient temperature 30 70 Relay output max AC 240V max 2 5A C300 mi...

Page 44: ...DC Max voltage 300V DC AC Max current 0 5A DC AC Figure 21 Oil level switch Notes 1 There is a triangle mark on the float indicating the sensor direction Before you install an oil level switch on a co...

Page 45: ...trol power lines refer to the drawing below cable box RC2 200 620AV cable box RC2 1020 1530AV cable box Figure 25 IP54 cable box Liquid injection system solenoid valve expansion valve additional cooli...

Page 46: ...ature and parallel systems system with long piping Hanbell specially designs a complete series of external oil separators OS series with characteristics of high separation efficiency and low pressure...

Page 47: ...caused by resonance Drawing Vertical OS40 65 Horizontal OS80 150 Figure 28 OS series external oil separator m External oil filter External oil filter is an optional accessory It is suggested to instal...

Page 48: ...or oil return port 47 Qmax Recom l min switch value l min selectable range for fixed switch mm 20 0 4 12 40 0 6 25 60 1 5 40 Figure 30 Oil flow switch Average pressure loss 0 4 bar at Qmax Hysteresis...

Page 49: ...Pt1000 sensor on motor coil as optional accessories This temperature sensor along with controller of the system monitor motor coil temperature and then control on off of liquid injection valve accordi...

Page 50: ...Insulation test voltage U is AC 1 5kV Compressors motor can be equipped with either Pt100 or Pt1000 sensor to precisely control liquid injection and maintain motor coil while running Please specify Pt...

Page 51: ...ngly recommended especially when the wiring length between VFD and motor exceeds 5m otherwise it might cause serious damage to the inverter or the motor Please discuss with your VFD providers whether...

Page 52: ...ck response while the temperature approaches to their set point thermistors must be connected in series to a controller INT69HBY in cable box as a guardian to protect compressor Alarm lamp for this pr...

Page 53: ...Those functions as speed control malfunction feedback VFD reset should be workable 2 Should follow the nameplate of compressor 3 Acceleration 50 60 sec from 0Hz to 50Hz deceleration vice versa 6 Comp...

Page 54: ...s that might happen at jobsites This table could be a guide for engineers when problems are found PROBLEMS POSSIBLE CAUSES REMEDY CORRECTIVE ACTION Sudden trip of motor thermistor sensor Low refrigera...

Page 55: ...er Check and clean the condenser Refrigerant overcharge Reduce the refrigerant charge Air moisture in refrigerant system Recover purify refrigerant and vacuum system Improper expansion valve Check and...

Page 56: ...ler is heavy due to high temperature chilled water so the liquid injection devices capacity should be selected or calculated enough to reduce the overheat of the compressor Calculating the cooling cap...

Page 57: ...d motor coil temperature is high This may lead to motor failure Therefore in applications mentioned above Pt100 or Pt1000 for liquid injection to motor is recommended instead Figure 43 Liquid injectio...

Page 58: ...ooler to reject heat from the cooling medium The basic water cooled oil cooling system is shown in Figure 47 Figure 47 Oil cooling by water Note 1 Please decide appropriate oil cooler capacity by refe...

Page 59: ...dditional middle connection is at a similar level to the intermediate pressure with a two stage system As a result of these features a screw compressor of this design can be combined with an additiona...

Page 60: ...59 Figure 50 Installation of ECO muffler Figure 51 System with economizer sub cooler Figure 52 System with economizer flash type sub cooler...

Page 61: ...on 1 Filter 6 Flow switch 11 Dryer 2 Compressor 7 Oil filter 12 Secondary cooler 3 Check valve 8 Oil cooler 13 Muffler 4 Sight glass 9 Expansion valve 5 Solenoid valve 10 Oil separator 7 4 Oil pump ap...

Page 62: ...uction pressure when pumping down should is 0 5kg cm2 c Time for pumping down should be shorter than 15 seconds d When doing pump down notice the high discharge temperature It should not go over 110 e...

Reviews: