HAMECH DTR KWH
5
When using these fuels the thermal efficiency drops, approximately
proportionally to the drop of n.c.v. (in relation to the basic fuel) and
problems with boiler maintenance.
Negligence in frequent cleaning of the boiler may lead to problems with
removal of impurities from heated boiler’s surfaces, decrease of flow in exhaust
channels and drop of boiler’s efficiency.
2.6. Technical data.
TABLE 1.
No.
Item
Unit
Thermal power
1 Rated thermal power
kW
55
110
180
2
Adapted for co-operation with the
unit
♦
AZSD-50
AZSD-100
AZSD-180
3
Rated thermal power together
with AZSD
kW
60*
90**
190***
4 Basic fuel for AZSD
Comminuted wood of up to 30 mm granulation and
30-50% humidity
5 Thermal power adjustment range
%
30 - 100
6 Heated boiler surface
m
2
5,5
11,5
21
7 Admissible static pressure
MPa
0,3
8 Max. temp. of outlet water
ºC
95
9 Required draft behind the boiler
Pa
>23
>26
>29
10
Average exhaust gas temp. at
the flue
ºC
200
11
Basic fuel consumption at
nominal power of AZSD
kg/h
24,1*
40,57**
55***
12
Thermal efficiency at nominal
power when coupled with AZSD
%
≥77,7
≥78,7
≥78,7
13 Weight with insulation
kg
600
1150
1750
14 Funnel height
•
m
8
12
12
15 Funnel diameter
•
mm
190
315
370
16 Water volume
l
180
350
800
*- at n.c.v. 12 028 kJ/kg
** - at n.c.v. 9 535 kJ/kg
*** - at n.c.v. 15955 kJ/kg
♦
- connection dimensions – see appropriate drawings
•
- with natural draft
Table 1 continued