Halton Max Ultra Circular (MUC) - Installation, commissioning and maintenance guide 9(31)
Version 1.0
All rights reserved © Halton
3
Installation
3.1
Before you start
3.1.1
Installation process
The installation is carried out by Halton Field Service or an approved partner.
Follow the installation process chart to install the Halton Max Ultra Circular (MUC) damper.
Fig.2. Halton Max Ultra Circular (MUC) installation process chart
3.1.2
Installation information
Installation options
There are three possibilities to position the damper. Sensors can be directed outwards, side or
inwards.
Safety distances and accuracy
Disturbances in the ductwork such as duct bends, T-branches and sound attenuators cause
turbulence and an uneven airflow. This can lead to fluctuation and inaccuracy in measurement
values.
NOTE:
The recommended safety distance is greater or equal to one duct diameter distance, to
ensure the optimal accuracy.
Halton Max Ultra Circular (MUC) technical performance:
•
Velocity range
0,5 — 10,0 m/s