Halton Max Ultra Circular (MUC) - Installation, commissioning and maintenance guide 22(31)
Version 1.0
All rights reserved © Halton
c.
Set the
AO1type
parameter to the value
Voltage / Current
.
d.
Set the
AO1rg
parameter to the value
0...10V / 2... 10 V
if
AI1type
is
Voltage
or to
0...20mA / 4...20mA
if
AI1type
is
Current
.
e.
Set the
AO1min
parameter to the value
0...15 m/s *CrossSection* 3600
.
NOTE:
The
AO1min
parameter is used only if
Ctrlsig
parameter has value
AF
.
f.
Set the
AO1max
parameter to the value
1...15 m/s *CrossSection*
NOTE:
The
AO1max
parameter is used only if
Ctrlsig
parameter has value
AF
.
9.
Set the
ActType
parameters to the value
Analog / LAC1.MA1
10.
Set the analog actuator feedback signal parameters.
a.
Set the
AI2type
parameter to
Voltage / Current
,
b.
Set the
AI2rg
parameter to
0...10V / 2...10V
if
AI1type
is
Voltage
or to
0...20mA /
4...20mA
if
AI1type
is
Current
.
11.
Set the analog actuator reference signal parameters.
a.
Set the
AO2type
parameter to the value
Voltage / Current
.
b.
Set the
AO2rg
parameter to the value
0...10V / 2...10V
if
AI1type
is
Voltage
or to
0...20mA / 4...20mA
if
AI1type
is
Current
.
12.
Set the PI regulator parameters.
a.
Set the
kp
parameter to the value
0...100.0
.
b.
Set the
ki
parameter to the value
0...100.0