Halton Max Ultra Circular (MUC) - Installation, commissioning and maintenance guide 31(31)
Version 1.0
All rights reserved © Halton
0xxxx, Coils
Register Name
Description
Value
00001
AI1type
Voltage or current type of AI1
'0' →
Voltage
'1' → Current
00002
AI1rg
Range of AI1
'0' → 0
-10V/0-20mA
'1' → 2
-10V/4-20mA
00003
AO1sig
Signal on AO1
'0' → Air flow
'1' → Damper position
00004
AO1actSP
Actual or set point value
'0' → Actual
1' → Set point
00005
AO1type
Voltage or current type of AO1
0' → Voltage
'1' → Current
00006
AO1rg
Range of AO1
'0' → 0
-10V/0-20mA
'1' → 2
-10V/4-20mA
00007
AI2type
Voltage or current type of AI2
'0' → Voltage
1' → Current
00008
AI2rg
Range of AI2
'0' → 0
-10V/0-20mA
'1' →
2-10V/4-20mA
00009
AO2type
Voltage or current type of AO2
'0' → Voltage
'1' → Current
00010
AO2rg
Range of AO2
'0' → 0
-10V/0-20mA
'1' → 2
-10V/4-20mA
00011
ActuatorType
Type of actuator
'0' → Analog
'1' → LAC
-1.MA1
1xxxx, Discreate inputs
Register Name
Description
Value
10001
ErrCode1
Wrong sensor connection or sensors
not connected
'0' → No error
'1' → Error
10004
ErrCode4
Air temperature sensor A is not
working
'0' → No error
'1' → Error
10005
ErrCode5
Air temperature sensor B is not
working
'0' → No error
'1' → Error
10006
ErrCode6
End switch position of LAC-1.MA1 is
faulty
'0' → No error
'1' → Error