Halton Max Ultra Circular (MUC) - Installation, commissioning and maintenance guide 30(31)
Version 1.0
All rights reserved © Halton
4xxxx, Holding register
Register Name
Description
Value
40004
AirFlowDB
Airflow regulation deadband, percentage of
AirFlowSP
0 .. 10000 → 0.00 ..
100.00%
40005
DamperSP
Setpoint for damper position
0 .. 10000 → 0.00 ..
100.00%
40023
AI1scaleMin
Analog input 1 minimum value
0 .. 65535 → 0 ..
65535 m
3
/h
40024
AI1scaleMax
Analog input 1 maximum value
0 .. 65535 → 0 ..
65535 m
3
/h
40025
AO1scaleMin
Analog output 1 minimum value
0 .. 65535 → 0 ..
65535 m
3
/h
40026
AO1scaleMax
Analog output 1 maximum value
0 .. 65535 → 0 ..
65535 m
3
/h
40030
Kp
K factor of PI regulator
0 .. 1000 → 0.0 ..
100.0
40031
Ki
I factor of PI regulator
0 .. 1000 → 0.0 ..
100.0
40905
SaveR
Save and take over “R” parameters
9055