Basic controller settings
Press the OK button to move to the next step. Press the ESC button to move to the previous step.
Change the parameters settings with left and right push buttons.
1.
Set the parameter
CtrlMode
to
Console / Modbus / Analog
.
2.
Set the parameter
CtrlSig
to
AF / Damper
3.
Set the parameter
DtID
to
#0 - #51
.
NOTE:
The installation factor
(DtID)
parameter values can be found in the
4.
Set the parameter
SP
to
Airflow or Damper position
.
NOTE:
If the parameter
CtrlMode
is set to the other value than
Console
, go back to step 1
and set
CtrlMode to Console
.
5.
Set the parameter
AirFlowDB
to
Deadband
.
NOTE:
If the parameter CtrlMode is set to
Modbus
, go back to step 1 and set
CtrlMode
to
Console
or
Analog
.
6.
Set the Modbus RTU parameters.
a.
Set
SlvID
parameter to the value
1...246
.
b.
Set the
Baud
parameter to the value
4k8 / 9k6 / 14k4 / 19k2 / 38k4 / 56k0 / 57k6 /
115k2
.
c.
Set the
Pr
parameter to the value
None / Even / Odd
.
7.
Set input for airflow or damper reference signal parameters.
a.
Set the
AI1type
parameter to the value
Voltage / Current
.
b.
Set the
AI1rg
parameter to
0..10V / 2..10V
if
AI1type
value is Voltage or
0..20mA/4..20mA
if
AI1type
is
Current
.
c.
Set the
AI1min
parameter to the value
0..15m/s*CrossSection*3600
.
d.
Set the
AI1max
parameter to the value
1..15m/s*CrossSection*3600
.
8.
Set AO1 parameters.
a.
Set the
AO1sig
parameter to the value
AirFlow / Damper
.
b.
Set the
AO1actSP
parameter to the value
Actual / SP
.