7
2. Troubleshooting
7-5
E
2.
Troubleshooting
In the Event of an Error
Perform the steps below:
1.
If the current error matches a symptom in the following table, correct it by following the instructions
provided.
2.
If the error does not match the symptoms in the table, contact your local distributor.
Please provide the distributor with the information on the MONITOUCH model, serial number,
symptom of the error, error message (if shown), etc.
Probable Symptoms
Symptom
Cause
Solution
MONITOUCH is connected
to the PLC; however,
communication fails.
“Communication Error:
Time-Out” appears on the
screen.
Probable causes are:
Solutions are:
1) Cables are not connected correctly or any
cable is disconnected.
1) Check the cable connection.
2) PLC parameter settings are not correct or
disagree with the MONITOUCH settings.
2) Recheck the PLC parameter settings.
3) The MONITOUCH is faulty.
3) Perform a self-loop test on the “I/O Test”
screen (page 6-5).
If the test is not successful, please return
the MONITOUCH to your local distributor
immediately.
Communications have been
successful. However,
opening a certain page
always causes a
“Communication Error: Error
code received” error.
The error code denotes a PLC error (NAK).
1) When the error code appears only on a
certain screen, a memory address that
does not exist on the PLC may be set on
the MONITOUCH screen.
1) Check if any address outside the allowable
range for PLC memory is set on the screen.
2) When the error code appears at power-on,
a memory address that does not exist on
the PLC may be set for communication
parameters, buffering area, initial macro,
etc.
2) Check if any address outside the allowable
range for PLC memory is set for
communication parameters, buffering area,
initial macro, etc.
Communications have been
successful. However,
“Communication Error:
Parity” or “Communication
Error: Framing” suddenly
occurs.
Noise may cause the error.
Check if appropriate measures are taken
against noise.
Example:
Check if communication and power cables are
bundled together.
Try to attach a ferrite core to the
communication cable.
Try to attach a noise filter to the power supply,
etc.
SYSTEM
F2
F3
F4
F5
F1
POWER
SYSTEM
F2
F3
F4
F5
F1
POWER
SYSTEM
F2
F3
F4
F5
F1
POWER
Summary of Contents for MONITOUCH V606e
Page 1: ...V606e SYSTEM F2 F3 F4 F5 F1 POWER V606e...
Page 9: ...11 Features 2 Models and Peripheral Equipment 3 System Composition Overview...
Page 15: ...1 6 3 System Composition Please use this page freely...
Page 28: ...2 12 5 Modular Jack MJ1 Please use this page freely...
Page 29: ...31 Mounting Procedure 2 Power Supply Cable Connection Installation...
Page 48: ...61 Operational Procedures 2 Main Menu Screen MONITOUCH Operations...
Page 65: ...71 Error Messages 2 Troubleshooting Error Correction...
Page 72: ...81 Inspection and Maintenance 2 Warranty Policy Inspection and Maintenance...
Page 76: ...8 4 2 Warranty Policy Please use this page freely...