![background image](http://html1.mh-extra.com/html/hakko-electronics/monitouch-v606e/monitouch-v606e_hardware-specifications_3295721042.webp)
5
3. n : 1 Connection (Multi-link 2)
5-3
Co
nne
3.
n : 1 Connection (Multi-link 2)
•
One PLC is connected to a maximum of four V606e units.
•
An original network is created where the V606e (Local Port 1) that is directly connected to the PLC
is the master station, and other three V606e units are slave stations. Only the master station
makes communications directly with the PLC, and the slave stations make communications with
the PLC via the master station.
•
Communications between the V606e master station and the PLC depend on the communication
speed set on the PLC. The maximum available speed for the V606e is 57600 bps, which is higher
than the one available with multi-link connection described in “4. n : 1 Connection (Multi-link).”
•
This multi-link connection is available with almost all the PLC models that support 1 : 1 connection
(refer to the Appendix).
(The connection between the master station and the PLC is the same as the one for 1 : 1
connection.)
•
Use the RS-485 2-wire connection between stations of the V606e. Please use Hakko Electronics’
multi-link 2 master cable (V6-MLT) for connection between the master station (Local Port 1) and
the slave station (Local Port 2).
•
The V606e and V6 series can be used together. The V6 series can be the master station.
(However, when V606e/V606/V606i is the master station, the slave station must be
V606e/V606/V606i. Also, depending on the hardware version of the V6 series, multi-link 2
connection may not be supported. Refer to the V6 Hardware Specifications.)
•
For more information on wiring and communication settings, refer to the PLC Connection Manual.
PLC
RS-232C
RS-422
RS-485
CN1
MJ1
CN1
CN1
CN1
SYSTEM
F2
F3
F4
F5
F1
POWER
SYSTEM
F2
F3
F4
F5
F1
POWER
SYSTEM
F2
F3
F4
F5
F1
POWER
SYSTEM
F2
F3
F4
F5
F1
POWER
Hakko Electronics’ cable
“V6-MLT” (3 m)
RS-485 connection
V606e master station
V606e slave station
V606e slave station
Local
Port 1
Local
Port 2
Local
Port 3
Local
Port 4
V606e slave station
Summary of Contents for MONITOUCH V606e
Page 1: ...V606e SYSTEM F2 F3 F4 F5 F1 POWER V606e...
Page 9: ...11 Features 2 Models and Peripheral Equipment 3 System Composition Overview...
Page 15: ...1 6 3 System Composition Please use this page freely...
Page 28: ...2 12 5 Modular Jack MJ1 Please use this page freely...
Page 29: ...31 Mounting Procedure 2 Power Supply Cable Connection Installation...
Page 48: ...61 Operational Procedures 2 Main Menu Screen MONITOUCH Operations...
Page 65: ...71 Error Messages 2 Troubleshooting Error Correction...
Page 72: ...81 Inspection and Maintenance 2 Warranty Policy Inspection and Maintenance...
Page 76: ...8 4 2 Warranty Policy Please use this page freely...