![Hakko Electronics MONITOUCH V606e Hardware Specifications Download Page 66](http://html1.mh-extra.com/html/hakko-electronics/monitouch-v606e/monitouch-v606e_hardware-specifications_3295721066.webp)
7
1. Error Message
7-1
E
1.
Error Message
There are five kinds of error messages displayed on the V series:
1.
Communication error
2.
Check
3.
Warning
4.
SYSTEM ERROR
5.
Touch switch is active
1.
Communication Error
* If the above error messages are displayed on the unit without establishing communication
between V606e and PLC, test the solution of remark “1.”
If the error occurs suddenly in communication, test the solution of remark “2.”
SYSTEM
F2
F3
F4
F5
F1
POWER
MENU
Communication Error
Time-Out
SYSTEM
F2
F3
F4
F5
F1
POWER
* When you go to [Comm. Parameter], bring
up the [Detail] tab window and set [Continue]
for [Comm. Err. Handling], a screen like the
one shown below is displayed.
Error Message
Contents
Solution
Remarks
Time-Out
Although a request to send is given to
the PLC, no answer is returned within
the specified time.
1. Check the communication parameters.
2. Check the cables and wiring.
1
3. Data may be disrupted because of noise.
Fix noise.
2
Parity
An error occurred in parity check.
1. Check the cables and wiring.
1
2. Data may be disrupted because of noise.
Fix noise.
2
Framing
Although the stop bit must be [1], it is
detected as [0].
1. Check the communication parameters.
2. Check the cables and wiring.
1
3. Data may be disrupted because of noise.
Fix noise.
2
Overrun
After one character is received, the next
character is received before internal
processing is completed.
1. Check the communication parameters.
1
2. Data may be disrupted because of noise.
Fix noise.
2
Check Code
The check code in the PLC response
was not correct.
1. Check the communication parameters.
1
2. Data may be disrupted because of noise.
Fix noise.
2
Summary of Contents for MONITOUCH V606e
Page 1: ...V606e SYSTEM F2 F3 F4 F5 F1 POWER V606e...
Page 9: ...11 Features 2 Models and Peripheral Equipment 3 System Composition Overview...
Page 15: ...1 6 3 System Composition Please use this page freely...
Page 28: ...2 12 5 Modular Jack MJ1 Please use this page freely...
Page 29: ...31 Mounting Procedure 2 Power Supply Cable Connection Installation...