DIP Switch (DIPSW) Setting
Set the terminating resistance for RS-422/485 connection with the DIP switch.
When setting the DIP switch, turn the power off.
* Set DIPSW1 to 4 and DIPSW8 (not used) to the OFF position.
Terminating Resistance Setting (DIPSW5, 6, 7)
•
When connecting the PLC at CN1 via RS-422/485 interface (2-wire connection), set DIPSW7 to
the ON position.
•
When connecting the PLC at CN1 via RS-422/485 interface (4-wire connection), set DIPSW5
and
7 to the ON position.
•
For the following connections at modular jack 1, set DIPSW6 to the ON position.
- Master station for multi-link 2 connection
- Temperature controller network/PLC2Way connection via RS-485
- Card Recorder: Connection with the CREC (optional)
- Serial extension I/O: Connection with the V-I/O (optional)
- Connection to the V606e at the termination of V-link connection via RS-485
CN1
MJ1
INPUT: 24VDC
CURRENT:0.4A
ASSEMBLED IN CHINA
C
US
E185413
Hakko Electronics Co., Ltd.
TYPE:V606eM*0
Ser No: ******* *
(3)
Rear View
DIP switch
ON
1
2
3
4
5
6
7
8
Not used
CN1 RD terminating resistance at pins 24 and 25
MJ1 (modular jack 1) terminating resistance
Not used
CN1 SD terminating resistance at pins 12 and 13
(*1)
Summary of Contents for MONITOUCH V606e
Page 1: ...V606e SYSTEM F2 F3 F4 F5 F1 POWER V606e...
Page 9: ...11 Features 2 Models and Peripheral Equipment 3 System Composition Overview...
Page 15: ...1 6 3 System Composition Please use this page freely...
Page 28: ...2 12 5 Modular Jack MJ1 Please use this page freely...
Page 29: ...31 Mounting Procedure 2 Power Supply Cable Connection Installation...
Page 48: ...61 Operational Procedures 2 Main Menu Screen MONITOUCH Operations...
Page 65: ...71 Error Messages 2 Troubleshooting Error Correction...
Page 72: ...81 Inspection and Maintenance 2 Warranty Policy Inspection and Maintenance...
Page 76: ...8 4 2 Warranty Policy Please use this page freely...