A
˅
NO
YES
Yes
Check the indoor mainboard.
No
If the voltage is of a constant
value of 0V DCto5V DC
YES
Measure the voltage between Jumpers 3 and
4 of IC1 on the indoor mainboard with a
multimeter.
NO
The outdoor mainboard is damaged;
Replace them with a new one.
Measure the AC voltage between positions 1
and 3 on the terminal of outdoor unit with a
multimeter.
If 230VAC is available but 310DC not,
the power module is damaged, replace it
with a new one.
Test the outdoor power supply (230VAC
and +310VDC) with a multimeter.
The outdoor mainboard is damaged; replace
it with a new one.
The indoor mainboard is damaged; replace
it with a new one.
If the value varies between 0 and 80 VAC,
the outdoor mainboard is damaged, replace it
with a new one.
If the value is constant at about 30V, the
indoor mainboard is damaged, replace it with
a new one.
If both 230VAC and 310DC are
available, measure
+12V(from7805) is available.
Service diagnosis
Domestic air conditioner
60
Summary of Contents for Z/N-Series
Page 11: ... Pinping diagrams Domestic air conditioner 4ˊPinping diagrams 9 ...
Page 12: ... Operation range Domestic air conditioner 5ˊOperation range 10 ...
Page 15: ...CN9 CN10 CN36 CN3 CN23 CN24 CN25 CN28 PCB 1 Wiring diagram Domestic air conditioner 13 ...
Page 17: ...Wiring diagram Domestic air conditioner 15 ...
Page 36: ...WARNING CAUTION Installations Domestic air conditioner 34 ...
Page 37: ...Installations Domestic air conditioner 35 ...
Page 38: ...Installations Domestic air conditioner 36 ...
Page 39: ...Installations Domestic air conditioner 37 ...
Page 40: ...Installations Domestic air conditioner 38 ...
Page 41: ...Installations Domestic air conditioner 39 ...
Page 42: ...Installations Domestic air conditioner 40 ...
Page 45: ...Pressurize for over 3 minutes at 4 2MPa After above Installations Domestic air conditioner 43 ...