11.4.4 Outdoor DC fan motor fault
Outdoor display LED1 flash 9 times
Method of DC fan motor is detected by checking the fan running condition and so on
Malfunction
Detection
Malfunction when the data of EEPROM is error or the EEPROM is damaged
Decision
Conditions
Supposed
Ƶ
DC fan motor protection dues to the DC fan motor faulty
Causes
Ƶ
DC fan motor protection dues to faulty PCB
Troubleshooting * Caution Be sure to turn off power switch before connect or disconnect connector, or parts damage
may be occurred.
Check whether Terminal on the outdoor
mainboard is well inserted.
Is it normal?
Yes
NO
Reinsert the terminals
Electrify the machine again and turn it
on in the Cool state with the remote
controller. check whether motor can
run
˛
Yes
Measure the voltage between 3 and 6 of
the terminal about 0-5v.
Is it normal?
N0
the motor of the outdoor unit is damaged and
needs replacing.
Measure the voltage between 1 and 3 of the terminal of
fan motor on the mainboard about DC310V, Measure
the voltage between 3 and 4 of the terminal about
DC15V. Measure the voltage between 5 and 3 of the
terminal about 1-6v.
NO
Is it normal?
The mainboard of the outdoor unit is
damaged and needs replacing
N0
Yes
Yes
Service diagnosis
Domestic air conditioner
53
Summary of Contents for Z/N-Series
Page 11: ... Pinping diagrams Domestic air conditioner 4ˊPinping diagrams 9 ...
Page 12: ... Operation range Domestic air conditioner 5ˊOperation range 10 ...
Page 15: ...CN9 CN10 CN36 CN3 CN23 CN24 CN25 CN28 PCB 1 Wiring diagram Domestic air conditioner 13 ...
Page 17: ...Wiring diagram Domestic air conditioner 15 ...
Page 36: ...WARNING CAUTION Installations Domestic air conditioner 34 ...
Page 37: ...Installations Domestic air conditioner 35 ...
Page 38: ...Installations Domestic air conditioner 36 ...
Page 39: ...Installations Domestic air conditioner 37 ...
Page 40: ...Installations Domestic air conditioner 38 ...
Page 41: ...Installations Domestic air conditioner 39 ...
Page 42: ...Installations Domestic air conditioner 40 ...
Page 45: ...Pressurize for over 3 minutes at 4 2MPa After above Installations Domestic air conditioner 43 ...