11.4.9 Overheat Protection For Discharge Temperature
Outdoor display: LED1 flash 8 times
Method of The Discharge temperature control is checked with the temperature being detected
Malfunction by the Discharge pipe thermistor
Detection
Malfunction when the compressor discharge temperature is above 110
ć
Decision
Conditions
Supposed
■
Electronic expansion valve defective
Causes
■
Faulty thermistor
■
Faulty PCB
Troubleshooting * Caution Be sure to turn off power switch before connect or disconnect connector, or
else parts damage may be occurred.
Electrify the machine again and turn it on with the remote controller,
then measure the temperature at the exhaust temperature sensor of
the compressor on the outdoor unit
The temperature exceeds
110
ć
shortly after the
machine starts up?
1) The cryogen may have been leaked during
installation, or there may be leakage in the piping
system.
2) There may be other causes to make the exhaust
temperature too high.
Malfunctions occur after running for some time even
though the measured temperature is below 110
ć
. Pull
out the exhaust sensor and measure its resistance at
standard temperatures according to the
resistance-temperature table
The results deviate
much?
The sensor is damaged. Replace the sensor
with a new one.
The outdoor mainboard is damaged and needs be
replaced
YES
NO
NO
YES
Service diagnosis
Domestic air conditioner
58
Summary of Contents for Z/N-Series
Page 11: ... Pinping diagrams Domestic air conditioner 4ˊPinping diagrams 9 ...
Page 12: ... Operation range Domestic air conditioner 5ˊOperation range 10 ...
Page 15: ...CN9 CN10 CN36 CN3 CN23 CN24 CN25 CN28 PCB 1 Wiring diagram Domestic air conditioner 13 ...
Page 17: ...Wiring diagram Domestic air conditioner 15 ...
Page 36: ...WARNING CAUTION Installations Domestic air conditioner 34 ...
Page 37: ...Installations Domestic air conditioner 35 ...
Page 38: ...Installations Domestic air conditioner 36 ...
Page 39: ...Installations Domestic air conditioner 37 ...
Page 40: ...Installations Domestic air conditioner 38 ...
Page 41: ...Installations Domestic air conditioner 39 ...
Page 42: ...Installations Domestic air conditioner 40 ...
Page 45: ...Pressurize for over 3 minutes at 4 2MPa After above Installations Domestic air conditioner 43 ...