14K 18K
1.
To bend a pipe, give the roundness as large as possible not to crush the pipe ,
ƽ
and the bending radius should be 30 to 40 mm or longer.
Connecting the pipe of gas side
fi
rst makes working easier.
ƽ
The connection pipe is specialized for R410A.
ƽ
Half union
Flare nut
Torque wrench
CAUTION:
Be careful that matters, such as wastes of sands,water,, etc. shall not enter the pipe.
Spanner
Forced fastening without careful centering may
damage the threads and cause a leakage of gas.
Pipe Diameter(
ǿ
)
Fastening torque
Liquid side6.35mm(1/4")
18N.m
Liquid/Gas side9.52mm(3/8")
42 N.m
Gas side 12.7mm(1/2")
55N.m
Gas side 15.88mm(5/8")
60 N.m
Connection of pipes
2.
In case the elevation B is more than 5m,
oil trap shoud be installed every 5~7m
Max. Length: B1 max =20m B2 max =20m
Max.Elevation: A1 max =15m A2 max =15m
In case the pipe total length (B1+B2) is more than
20m, the refrigerant should be charged, according
to 20 g/m.
B
Outdoor unit
Indoor unit
A1
B1
Indoor unit
A2
B2
Outdoor unit
Indoor unit
B1
Indoor unit
B2
Outdoor unit
Indoor unit
Oil trap
A3
A3 max =15m
(B1+B2) max =30m
Outdoor unit
Indoor unit
A1
B1
Indoor unit
A2
B2
CAUTION
Indoor unit
Be careful that matters, such as wastes of sands, etc. shall not enter the pipe. The standard pipe
length of each indoor unit is 5m. If total pipe length is over 20m, the function of the unit will be
affected, charge more refrigerant is needed, according to 20 g/m. But the charge of refrigerant
must be conducted by professional air conditioner engineer. Before adding additional refrigerant,
perform air purging from the refrigerant pipes and indoor unit using a vacuum pump,then charge
additional refrigerant.
Installations
Domestic air conditioner
42
Summary of Contents for Z/N-Series
Page 11: ... Pinping diagrams Domestic air conditioner 4ˊPinping diagrams 9 ...
Page 12: ... Operation range Domestic air conditioner 5ˊOperation range 10 ...
Page 15: ...CN9 CN10 CN36 CN3 CN23 CN24 CN25 CN28 PCB 1 Wiring diagram Domestic air conditioner 13 ...
Page 17: ...Wiring diagram Domestic air conditioner 15 ...
Page 36: ...WARNING CAUTION Installations Domestic air conditioner 34 ...
Page 37: ...Installations Domestic air conditioner 35 ...
Page 38: ...Installations Domestic air conditioner 36 ...
Page 39: ...Installations Domestic air conditioner 37 ...
Page 40: ...Installations Domestic air conditioner 38 ...
Page 41: ...Installations Domestic air conditioner 39 ...
Page 42: ...Installations Domestic air conditioner 40 ...
Page 45: ...Pressurize for over 3 minutes at 4 2MPa After above Installations Domestic air conditioner 43 ...