9.1 According to the temperature measured by Td, the unit will adjust compressor frequency when
discharging temperature is overheat. When spraying refrigerant cannot efficiently decrease
discharging temperature, the system will make decrease-frequency protection.
9.2 When Td is over 110
℃
, the frequency will reduce 10Hz for every 120 seconds. When the output
frequency has become the low limit, Td is still over 110
℃
, the unit will stop.
10. Oil return operation
10.1 Oil return operation in cooling
Entering condition:
Indoor thermostat OFF time is over 30 minutes (after oil return operation, time again from
beginning).
In cooling mode, compressor runs for 1 hour in all (after oil return operation, time again from
beginning).
Operation procedure:
After oil return signal has been sent to indoor for 30 seconds, the unit will begin oil return operation.
Compressor running frequency is the oil return frequency, outdoor EEV open angle does not
change and quit oil return 4 minutes later, then resume the frequency before oil return operation,
finally, send oil return finish signal to indoor unit.
10.2 Oil return operation in heating
Entering condition:
Indoor thermostat OFF time is over 30 minutes (after oil return operation, time again from
beginning).
In heating mode, compressor runs for 1 hour in all (after oil return operation, time again from
beginning).
Operation procedure:
After oil return signal has been sent to indoor for 30 seconds, the unit will begin oil return operation.
Compressor running frequency is the oil return frequency, outdoor EEV open angle is the special
angle for heating oil return and quit oil return 4 minutes later, then resume the corresponding base
angle due to the indoor capacity.
11. Compressor overheat protection
Values saved in EEPROM:
Parameter
Current protection data
unit
Data out of factory
Actual data
Over current protection
Over_c (Pr-24)
%
130
13*130%=16.9(A)
Over load protection
Ov_load (Pr-23)
%
106
13*100%=13(A)
Overcurrent stall
protection
Oc_stall (Pr-26)
%
96
13*88%=11.5(A)
Overload fixed
frequency protection
value
Ov_load2 (Pr-28)
%
100
13*96%=12.5 (A)
Rated current
Rate_c (Pr-20)
A
13
13(A)
12. Input protection signal
High/low pressure switch protection:
When input of pressure switch is 0, that shows no protection.
When input of pressure switch is 1 for 1 minute, that shows high pressure protection, and
compressor stops, then there will be failure alarm signal. If alarm has been solved, the protection
>a__WcU[S^ <[c >a`V[e[a`Wc
-103-
Summary of Contents for H-MRV AF092FCBHA
Page 121: ... _ VbTZR Zb _ UZdZ_ Vb AU242FHBHA PCB top layer printed diagram 121 ...
Page 122: ... _ VbTZR Zb _ UZdZ_ Vb AU242FHBHA PCB bottom layer printed diagram 122 ...
Page 127: ... _ VbTZR Zb _ UZdZ_ Vb AU482FIBHA high voltage PCB printed diagram 127 ...
Page 131: ... _ VbTZR Zb _ UZdZ_ Vb AU482FIBHA low voltage PCB printed diagram 131 ...
Page 152: ... a__WcU S c a V e a Wc AB092 182FCBHA PCB printed diagram 152 ...
Page 156: ... a__WcU S c a V e a Wc AE FCBKA PCB printed diagram 156 ...
Page 199: ...MEMO Commercial Air Conditioner ...