temperature, and send it to
outdoor, the other control is
similar with normal.
SW05
Swing
trial
run Indoor trial run in swing
mode,the control is the same
as swing trial run with remote
controller.
[set]
SW01“02”, SW02“05”, press SW04 for more than
2 seconds, after set of trial run success, LD will
always display –F until the function is cancelled.
[cancel]
in trial run state, SW01“02”, SW02“05”, press
SW05
Uniform running Indoor is uniform running
The indoor running mode is
corresponding with the setting
or memory of remote
controller.
[set]
SW01“02”, SW02“05”, press SW04 for more than
2 seconds, after set of trial run success, LD will
display FF for 5 seconds.
[cancel]
cancel according to operation of remote
controller
Uniform stop
Indoor uniform stops
[set]
SW01“02”, SW02“06”, press SW05 for 2
seconds, after set success, LD will display FF for
5 seconds.
[cancel]
cancel according to operation of remote
controller
Indoor PMV
fully open
compelled
Indoor PMV fully open
compelled in 2 minutes
[set]
SW01“2”, SW02“10”, press SW04 for more than
2 seconds
[confirmation]
in 2 minutes, 7-segment LED of base board I/F
will display “FF” all the time
[cancel]
the control software will recover PMV to normal
open degree after 2 minutes
(
after indoor
software receives the signal of fully open from
outdoor, PMV will fully open only in 2 minutes.
)
Rated running
Set the unit rated running
[set]
SW01“02”, SW02“11”, press SW05 for more than
2 seconds, after setting success, LD will display
–F, shows that the unit may enter rated running
mode, afterwards you can set SW06,
SW07.SW06 is used for increasing frequency,
while SW07 is used for decreasing frequency.
[cancel]
cancel according to operation of remote
controller
Outdoor PMV1
fully open,
closed function
Outdoor PMV1 compelled fully
open or close in 2 minutes
[set]
SW01“3”, SW02“9”, press SW04 for more than 2
seconds
[confirmation]
in 2 minutes, 7-segment LED of base board I/F
will display “FF” all the time
[cancel]
the control software will recover PMV to normal
open degree after 2 minutes
(
after indoor
software receives the signal of fully open from
outdoor, PMV will fully open only in 2 minutes.
)
>a__WcU[S^ <[c >a`V[e[a`Wc
-137-
Summary of Contents for H-MRV AF092FCBHA
Page 121: ... _ VbTZR Zb _ UZdZ_ Vb AU242FHBHA PCB top layer printed diagram 121 ...
Page 122: ... _ VbTZR Zb _ UZdZ_ Vb AU242FHBHA PCB bottom layer printed diagram 122 ...
Page 127: ... _ VbTZR Zb _ UZdZ_ Vb AU482FIBHA high voltage PCB printed diagram 127 ...
Page 131: ... _ VbTZR Zb _ UZdZ_ Vb AU482FIBHA low voltage PCB printed diagram 131 ...
Page 152: ... a__WcU S c a V e a Wc AB092 182FCBHA PCB printed diagram 152 ...
Page 156: ... a__WcU S c a V e a Wc AE FCBKA PCB printed diagram 156 ...
Page 199: ...MEMO Commercial Air Conditioner ...