Closing the cycle can avoid indoor freezing.
When the temperature measured by the indoor coil temperature coil is too low, the unit will enter
anti-freezed operation and be set under the below conditions.
Anti-freezed operation start condition:
If accumulative operation time is over 10 minutes at one temperature, the system will make the
thermostat OFF compulsorily until the anti-freezed function can reach stop condition.
Anti-freezed operation stop condition:
The time is over 10 minutes when the temperature rises upto one certain temperature.
2. Dry operation mode
2.1
Temeprature control range: 16~30
℃
, and control precision:
±
1
℃
2.2 Characteristic of electronic expansion valve (EEV):
as the same as that of cooling mode.
2.3 Fan speed control
Auto: Tr>Ts+1 high speed
Ts+1>Tr
≥
Ts low speed
Ts>Tr stop fan motor in 3 minutes, 3 minutes later, low speed
When fan speed changes from low to high,there is no delay, and when changing from high to low there is
30-second delay.
Thermostat OFF: fan motor stops in 3 minutes, meanwhile the valve goes back to standby angle, and 3
minutes later, it is low speed.
Fan speed adjustment by hand: when unit is running, you can set High/Med/Low/Auto speed due to
request.
2.4 No temperature compensation in Dry mode
2.5 Anti-freezed protection:
as the same as that of cooling mode.
3. Heating mode
3.1
Temeprature control range: 16~30
℃
, and control precision:
±
1
℃
3.2 Characteristic of electronic expansion valve (EEV):
as the same as that of cooling mode, but the
open angle is different.
3.3 Fan speed control
Auto speed:
Heat mode:
TA-TS +1
Super low speed
0
low speed
-1
med speed
-2
high speed
When fan speed changes from low to high,there is no delay, and when changing from high to low there is
30-second delay.
Thermostat OFF: EEV delays to close, after the fan motor enters super low speed, the thermostat will be
OFF.
>a__WcU[S^ <[c >a`V[e[a`Wc
-106-
Summary of Contents for H-MRV AF092FCBHA
Page 121: ... _ VbTZR Zb _ UZdZ_ Vb AU242FHBHA PCB top layer printed diagram 121 ...
Page 122: ... _ VbTZR Zb _ UZdZ_ Vb AU242FHBHA PCB bottom layer printed diagram 122 ...
Page 127: ... _ VbTZR Zb _ UZdZ_ Vb AU482FIBHA high voltage PCB printed diagram 127 ...
Page 131: ... _ VbTZR Zb _ UZdZ_ Vb AU482FIBHA low voltage PCB printed diagram 131 ...
Page 152: ... a__WcU S c a V e a Wc AB092 182FCBHA PCB printed diagram 152 ...
Page 156: ... a__WcU S c a V e a Wc AE FCBKA PCB printed diagram 156 ...
Page 199: ...MEMO Commercial Air Conditioner ...