Troubleshooting: Continuous Fan / Accessories Sequence of Operation
LED: SLOW FLASH RATE REMAINS
UNCHANGED THROUGHOUT SEQUENCE.
MANUAL FAN SELECTION MADE AT THERMOSTAT.
CONTROL (G) ENERGIZES SYSTEM FAN AT FAN
SPEED. EAC TERMINAL IS ENERGIZED.
THERMOSTAT CALLS FOR HEAT (W).
THERMOSTAT CALLS FOR COOLING.
SYSTEM FAN SWITCHED TO COOL SPEED.
EAC TERM. REMAINS ON.
THERMOSTAT OPENS.
THERMOSTAT OPENS.
MANUAL FAN SELECTION MADE AT THERMOSTAT.
CONTROL (G) ENERGIZES SYSTEM FAN AT FAN
SPEED. EAC TERM. ENERGIZED.
SYSTEM FAN SWITCHES TO HEAT SPEAD AFTER 30
SECOND DELAY. EAC AND HUM TERMINALS REMAIN ON.
SYSTEM FAN CONTINUES FAN SPEED
WITHOUT INTERRUPTION. EAC TERMINAL
REMAIN ON. HUM TERMINALS ARE ENERGIZED
WITH COMBUSTION AIR BLOWER.
HUM. TERMINALS OFF AFTER POST PURGE
BY COMBUSTION AIR INDUCER. SYTEM FAN
SWITCHES TO FAN SPEED AFTER BLOWER
OFF DELAY. EAC CONTINUES WITHOUT
INTERUPTION.
NO
NO
YES
YES