Page 44
31-5000729 Rev. 0
For safety, connect a shut-off valve between the
manometer and the gas tap to permit shut off of gas
pressure to the manometer.
IMPORTANT
Follow the steps below and use Figure 51 as a reference.
Gas manifold Kit 10L34 provides additional components if
needed.
1.
Connect the test gauge positive side “+“ to manifold
pressure tap on gas valve.
2.
Tee into the gas valve regulator vent hose and connect
to test gauge negative “-”.
3.
Start unit and let run for 5 minutes to allow for steady
state conditions.
4.
After allowing unit to stabilize for 5 minutes, record
manifold pressure and compare to value given in Table
14.
5.
Shut unit off and remove manometer as soon as an
accurate reading has been obtained. Take care to
remove barbed fitting and replace threaded plug.
6.
Start unit and perform leak check. Seal leaks if found.
Capacity
Gas
Manifold Pressure in. w.g.
Supply Line Pressure
in. w.g.
0-10,000 ft.
0-4500 ft.
4501-5500 ft.
5501-6500 ft.
6501-7500 ft. 7501-10000 ft.
All Sizes
Natural
3.5
3.3
3.2
3.1
3.5
4.5
13.0
LP /
Propane
10.0
9.4
9.1
8.9
10.0
11.0
13.0
NOTE
: A natural to LP propane gas changeover kit is necessary to convert this unit. Refer to the changeover kit installation
instruction for the conversion procedure.
Table 14. Manifold and Supply Line Pressure 0-10,000 ft.
(+)
(
−
)
Gas Valve Regulator
Vent Hose
(to burner box)
2” Long Square Tubing
(remove for manifold adjustment)
Tee
10” Long
Square
Tubing
Measuring Device
Barbed Fitting
Manifold Pressure Outlet
Negative Barbed Fitting
(remove for manifold adjustment)
Figure 51.