Troubleshooting: Heating Sequence of Operation
NORMAL HEATING MODE
ABNORMAL HEATING MODE
POWER ON
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
CONTROL SELF CHECK OKAY?
IS POLARITY CORRECT?
IS THERE A PROPER GROUND?
ROLLOUT SWITCH CLOSED?
BURNER OFF?
IS VOLTAGE
ABOVE 70 VOLTS?
NORMAL OPERATION:
LED SLOW FLASH
THERMOSTAT CALLS FOR HEAT:
LED SLOW FLASH
PRIMARY LIMIT SWITCH CLOSED?
IS COMBUSTION AIR
PRESSURE SWITCH OPEN?
IS COMBUSTION AIR INDUCER
ENERGIZED?
HAS COMBUSTION AIR PRESSURE
SWITCH CLOSED IN 2.5 MINUTES?
CONTINUED NEXT PAGE
GAS VALVE OFF. COMBUSTION AIR INDUCER OFF.
INDOOR BLOWER DELAY OFF.
LED SLOW FLASH
(RESET CONTROL BY TURNING MAIN POWER OFF.)
LED FLASHES CODE 1
-
POLARITY REVERSED.
LED FLASHES CODE 2
-
IMPROPER GROUND.
LED FLASHES CODE 13
- LOW LINE VOLTAGE.
CONTROL WILL NOT RESPOND TO A CALL FOR
HEATING UNTIL VOLTAGE RISES ABOVE 75 VOLTS.
LED FLASHES CODE 8
- ROLLOUT SWITCH
OPEN. GAS VALVE OFF. COMBUSTION
AIR INDUCER ON. INDOOR BLOWER ON.
SEQUENCE HOLDS UNTIL ROLLOUT SWITCH
CLOSES AND POWER IS RESET OR T’STAT IS
INTERRUPTED FOR MINIMUM OF 1 SECOND.
LED FLASHES CODE 12
- FLAME SENSED
WITHOUT GAS VALVE ENERGIZED. GAS VALVE OFF.
COMBUSTION AIR INDUCER ON. INDOOR BLOWER
ON HEATING SPEED.
LED FLASHES CODE 7
- PRIMARY
LIMIT OPEN. COMBUSTION AIR
INDUCER OFF.I NDOOR BLOWER ON
LED FLASHES CODE 11
- PRESSURE
SWITCH CLOSED. GAS VALVE OFF
COMBUSTION AIR INDUCER OFF.
INDOOR BLOWER OFF WITH DELAY.
(Sequence holds until pressure switch
opens or thermostat resets control.)
LED FLASHES CODE 9
- PRESSURE SWITCH
FAILED TO CLOSE OR OPENED DURING HEAT
DEMAND. PRESSURE SWITCH IS IN WATCHGUARD
MODE. GAS VALVE OFF. COMBUSTION AIR
INDUCER OFF. INDOOR BLOWER OFF WITH
DELAY. IS 5-MINUTE RESET PERIOD COMPLETE?