Page 54
31-5000729 Rev. 0
Troubleshooting: Cooling Sequence of Operation
NORMAL HEATING MODE
ABNORMAL HEATING MODE
POWER ON
NO
NO
NO
NO
IGNITION CONTROL MAIN POWER ON.
IS POLARITY CORRECT?
IS THERE A PROPER GROUND?
ROLLOUT SWITCH MONITORED CONTINUOUSLY.
IS ROLLOUT SWITCH CLOSED?
IS VOLTAGE
ABOVE 70 VOLTS?
LED: SLOW FLASH RATE REMAINS
UNCHANGED THROUGHOUT COOLING CYCLE.
COMPRESSOR CONTACTOR AND SYSTEM
FAN ENERGIZED WITH 2-SECOND DELAY
(COOLING SPEED)
LED FLASHES CODE 1
- POLARITY REVERSED.
CONTROL WILL CONTINUE TO CALL FOR COOLING
IN THIS CONDITION.
LED FLASHES CODE 13
- LOW VOLTAGE.
CONTROL WILL CONTINUE TO CALL FOR
COOLING IN THIS CONDITION.
LED FLASHES CODE 8
- ROLLOUT SWITCH OPEN. GAS
VALVE OFF. COMBUSTION AIR INDUCER ON. INDOOR
BLOWER ON. SEQUENCE HOLDS UNTIL ROLLOUT
SWITCH CLOSES AND MAIN POWER IS INTERRUPTED
OR THERMOSTAT IS CYCLED OFF/ON FOR 1 SEC. MIN.
LED FLASHES STEADY
- CIRCUIT BOARD FAILURE
GAS VALVE OFF. COMBUSTION AIR INDUCER OFF.
INDOOR BLOWER OFF WITH NORMAL DELAY.
INTERRUPT MAIN POWER TO RESET CONTROL.
THERMOSTAT OPENS.
THERMOSTAT CALLS FOR COOLING.
YES
YES
YES
YES
YES
COMPRESSOR OFF.
SYSTEM FAN AND EAC TERM. OFF
WITH 45-SECOND DELAY.
CONTROL SELF DIAGNOSTIC CHECK. IS
CONTROL OPERATING NORMALLY?
LED FLASHES CODE 2
-
IMPROPER GROUND
.
CONTROL WILL CONTINUE TO CALL FOR COOLING
IN THIS CONDITION.