Faults and treatment methods
7.1 Fault Code Query
(01 represents the A system,02 represents the B system)
S/N
Fault code
Fault description
Remarks
1
E01
Fault in air-condition flow switch
One lock
2
E05
(
-01/02/
)
Compressor module three-phase AC input phase
sequence mission protection
4 times in 60min,
locked.
3
E06
Three-phase AC input phase sequence error protection One lock
4
E07
Fault in return water temperature sensor
recoverable
5
E08
Fault in outlet water temperature sensor
recoverable
6
E09
Fault in outdoor ambient temperature sensor
recoverable
7
E15
Fault in communication of wired controller
recoverable
7
E16
Fault in communication of main board
recoverable
8
E17
(
-01/02
)
Fault in communication between compressor module
and main board
recoverable
9
E18
(
-01/02
)
Fault in communication between
fan module and main board
recoverable
10
E20
(
-01/02
)
The hardware transient overcurrent of the variable
frequency side of the system compressor module
4 times in 60min,
locked.
11
E21
(
-01/02
)
Instantaneous overcurrent detection of the variable
frequency side software of the system compressor
module
4 times in 60min,
locked.
12
E22
(
-01/02
)
The heat sink of the system compressor module is too
hot
4 times in 60min,
locked.
13
E23
(
-01/02
)
The system compressor module overloading
4 times in 60min,
locked.
14
E24
(
-01/02
)
The system compressor module undervoltage
4 times in 60min,
locked.
15
E25
(
-01/02
)
The system compressor module overvoltage
4 times in 60min,
locked.
16
E26
(
-01/02
)
The system compressor module variable frequency
side current detection circuit abnormal
4 times in 60min,
locked.
17
E27
(
-01/02
)
The system compressor module instantaneous power
failure
4 times in 60min,
locked.
18
E28
(
-01/02
)
Abnormal power supply on the control panel of the
system compressor module
4 times in 60min,
locked.
19
E29
(
-01/02
)
The system compressor module out-of-step
4 times in 60min,
locked.
20
E30
(
-01/02
)
Abnormal temperature sensor of compressor module
4 times in 60min,
locked.
21
E31
(
-01/02
)
The software transient overcurrent of the rectifier side
of the system compressor module
4 times in 60min,
locked.
22
E32
(
-01/02
)
The system compressor module rectifier side current
detection circuit abnormal
4 times in 60min,
locked.
23
E33
(
-01/02
)
The hardware transient overcurrent of the rectifier side
of the system compressor module
4 times in 60min,
locked.
24
E34
(
-01/02
)
Failed in the compressor module startup
4 times in 60min,
locked.
25
E37
(
-01/02
)
The system fan module overvoltage
4 times in 60min,
locked.
26
E38
(
-01/02
)
The system fan module undervoltage
4 times in 60min,
locked.
27
E39
(
-01/02
)
The system fan module software flow - limiting
operation
4 times in 60min,
locked.
28
E40
(
-01/02
)
System fan module software overcurrent protection
4 times in 60min,
locked.
29
E41
(
-01/02
)
System fan module hardware overcurrent protection
4 times in 60min,
locked.
30
E42
(
-01/02
)
System fan module NTC over-temperature protection
4 times in 60min,
locked.
31
E43
(
-01/02
)
System fan module AD detected abnormal shutdown of
the circuit
4 times in 60min,
locked.
32
E44
(
-01/02
)
The system fan module starts unsuccessfully or stops
4 times in 60min,