7
Model
Item
CA0100EAND
CA0130EAND
Cooling
Cooling capacity
kW
98
130
Power input
kW
28.9
38.4
Running current
A
53.2
75.4
Heating
Heating capacity
kW
103
135
Power input
kW
28.7
38.2
Running current
A
52.8
75
EER
3.39
3.39
COP
3.59
3.53
Max.Power input
kW
45.6
56
Max. running current
A
82.5
110
Power supply
3N/380V/50Hz
3N/380V/50Hz
Power factor
0.85
0.85
Refrigerant throttle type
Electronic expansion valve
Capacity control
33%,67%,100%
25%,50%,75%,100%
Compressor
Brand
DAIKIN
DAIKIN
Type
Scroll comprossor
Quantity
3
4
Input power
KW
27
36
Refrigerant
Type
R410A
Charge
kg
5.8*3
5.8*4
Air side heat
exchanger
Type
(Slit fin & efficient inner grooved copper tube)Inner grooved
copper pipe & hydrophilic aluminum fin coil
Fan power
KW
2.3
3
Air volume
m³/h
127
0
0×3
127
0
0×4
Fan type
Axial flow fan
Fan quantity
3
4
Water side heat
exchanger
Type
Shell & Tube heat exchanger
Rated water flow
m³/h
17.7
24
Inlet/outlet pipe
R 2"
(external screw thread)
R 2 1/2"
(external screw thread)
Water dirt coefficient
m2.
℃
/KW
0.018
0.018
Standard pressure
Mpa
1.0
1.0
Water resistance
kPa
50
60
Sound pressure level
1m away
dB(A)
67
68
Sound power level
1m away
dB(A)
85
86
External dimension
Unit length
mm
2060
2060
Unit width
mm
1603
1603
Unit height
mm
2170
2170
Package
dimension
Unit length
mm
2200
2200
Unit width
mm
1650
1650
Unit height
mm
2280
2280
Weight
Unit weight
kg
960
1090
Gross weight
kg
990
1125
Operation weight
kg
1010
1245
Safety & functional
protections
High/low Pressure Protection,Water Lackage delay Protection, Freeze Protection,Overload &
Overheat Protection, Phase Loss, Phase Sequence Protection
Note:
1. Nominal refrigerating condition: water outlet temperature is 7°C, ambient temperature is 35°C, and water flow is 0.172[m3/
(h·kW)].
2. Nominal heating condition: water outlet temperature is 45°C, ambient temperature is 7°C for dry bulb and 6°C for wet
bulb, and water flow is listed in the above table.
3. Unit operating range: conforming to GB/T 18430.1& GB/T 18430.2.
4. Scaling factor of circulating water: 0.018m2·°C/kW.
5. The specifications in the table may vary with changes in product design without prior notice.
Model
Summary of Contents for CA0035EAND
Page 1: ...1 Service Manual AIR COOLED MODULAR CHILLER SYJS 05 2021 B Edition 2021 05 ...
Page 10: ...8 4 Dimension CA0035EAND 6 Unit Base Diagram ...
Page 12: ...10 CA0100EAND CA0130EAND 7 Unit Base Diagram 5 2 8 1 0 5 5 1 1320 0 7 1 2 ...
Page 37: ...35 8 Wiring Diagram ...
Page 38: ...36 ...
Page 39: ...37 ...
Page 40: ...38 ...