7.3 Secondary parameter interface and setting
Press
[Select] key
or to select the secondary parameter, press
[
OK] to enter
the input password interface. (Initial password: 8676). This general user can not
enter. Need to be set up by professionals.
Password input method is as follows: Select the system parameters, the first bit of the password will be anti-black
display, press
[
modify]
or will be 1 or minus 1, to reach the value, press
[
SELECT] key the cursor will
move to the next number and anti-black display, the same way, modify the value.
1. After all four password values are set, press
[
Enter] to enter the system secondary parameter interface, as
shown below.
A .When the [Select] key is selected to set the water protection temperature parameter, the water protection
temperature parameter column is displayed in reverse black, and press
[
Modify]
or to set between
4 ~ 9
O
C.
B: Press [SELECT]
or to select the defrost interval parameter when the defrost interval parameter is set,
and then press
[
Modify]
or to set between 20 ~ 120min. When the defrost interval is set to "-", the setting
is invalid and the unit is operated at the adaptive defrost interval.
C: When the [Select key] is selected to set the defrost time parameter, the defrost time parameter bar is
displayed in reverse black, and press
[
Modify]
or to set it between 5 ~ 16min.
D: Press [SELECT]
or to select the defrost exit temperature parameter, the defrost exit temperature
parameter bar is reverse black display, and then press
[
Modify]
or to set between 10 ~ 20
O
C.
2. Press [SELECT]
or to enter the
second system parameter setting interface.
A: Press [SELECT]
or to select the call restart function when the call restart function bar is displayed
in black, press
[
Modify]
or to set "allow" or "cancel". In the "allow" state, the unit in the run-time if the
sudden power off, the unit can automatically operate according to the original state, without human operation; If
you select "Cancel" , the system is not operation after powered on, the default value is " cancel"
B: Press [SELECT]
or to select the time limit setting function, the time setting function bar is displayed
in reverse black, press [Enter] to enter time limit setting interface.
I. When [Select] is selected to set the number of days used, it has been displayed in days with the number of
days. Press [Modify]
or to set between 00-1999.
II. Press [SELECT]
or to select the number of days to set the time limit, the number of days in the number
of days to reverse the display, press
[
Modify]
or can be set between ----- 1999. In the "----" to cancel the
time limit function.
3. Press [SELECT]
or
to select the password for setting the secondary password, press [Enter] to enter
the password change interface, press [SELECT]
or to select the password , Press
[
Modify]
or
to change the password between 0 ~ 9, change the password and press [Enter] to confirm, and press [Exit] to
return to set the secondary password function
Enter a secondary password
****
Water protection temperature: 5
O
C
Defrost interval: 45
Defrost time: 8
Defrost exit temperature: 10
O
C
Call restart: Cancel
Time setting
Set the secondary password
Three level parameters
Using days: 0
Time limit days:-------
Summary of Contents for CA0035EAND
Page 1: ...1 Service Manual AIR COOLED MODULAR CHILLER SYJS 05 2021 B Edition 2021 05 ...
Page 10: ...8 4 Dimension CA0035EAND 6 Unit Base Diagram ...
Page 12: ...10 CA0100EAND CA0130EAND 7 Unit Base Diagram 5 2 8 1 0 5 5 1 1320 0 7 1 2 ...
Page 37: ...35 8 Wiring Diagram ...
Page 38: ...36 ...
Page 39: ...37 ...
Page 40: ...38 ...