58
Data type specification
Frame Format
Each frame data transmission formats
Remark
Set system address by IGU 21
Data type
Specification
Readed Value (A)
Denoted value (B)
Conversion formula
Temperture
0 - 30000
-100°C - 200°C
B=(A/100)-100
Current
0 - 10000
0 A - 100 A
B=A/100
Voltage
0 - 10000
0 V - 100 V
B=A/100
Pressure
1 - 10000
1 kPa - 10000 kPa
B=A
PMV opening angle
1 - 10000
1 - 10000
B=A
Error code
1 - 99
E01 - E99, 0 No Error
DI, on-off input
0 - off, 1 - on
DO, on-off output
0 - off, 1 - on
Startup & Shutdown
0 - shutdown, 1 - startup
Mode
0 - cooling mode , 2 - heating mode
Model
0x27 - CA0130EAND
System Address
Function Code
Data
The low byte CRC check
The High byte CRC check
1 byte
1 byte
N bytes
1 byte
1 byte
System Address
Gatway Address
Range
1-32
Function Code
Read or write function
Data
Communication data
CRC check
Each frame data error checking
Communication Address is used to define different sets of data within the same
system
Remark
Data address
01000- 01400
Master unit's data
Set it by Chiller PCB DIP
SW401
Data address
02000- 02400
Slave 1 unit's data
To
Data address
16000- 16400
Slave 15 unit's data
17.3 Comuunication address
Summary of Contents for CA0035EAND
Page 1: ...1 Service Manual AIR COOLED MODULAR CHILLER SYJS 05 2021 B Edition 2021 05 ...
Page 10: ...8 4 Dimension CA0035EAND 6 Unit Base Diagram ...
Page 12: ...10 CA0100EAND CA0130EAND 7 Unit Base Diagram 5 2 8 1 0 5 5 1 1320 0 7 1 2 ...
Page 37: ...35 8 Wiring Diagram ...
Page 38: ...36 ...
Page 39: ...37 ...
Page 40: ...38 ...