6
Item
CA0035EAND
CA0070EAND
Cooling
Cooling capacity
kW
30
65
Power input
kW
9.4
19.2
Running current
A
15.8
34.6
Heating
Heating capacity
kW
33
70
Power input
kW
9.6
19.1
Running current
A
16.2
34.4
EER
3.19
3.39
COP
3.44
3.66
Max.Power input
kW
16.3
28
Max. running current
A
27.5
55
Power supply
3N/380V/50Hz
3N/380V/50Hz
Power factor
0.85
0.85
Refrigerant throttle type
Electronic expansion valve
Capacity control
100%
50%,100%
Compressor
Brand
DAIKIN
DAIKIN
Type
Scroll comprossor
Quantity
1
2
Input power
KW
9
18
Refrigerant
Type
R410A
Charge
kg
5.5
6*2
Air side heat
exchanger
Type
(Slit fin & efficient inner grooved copper tube)Inner grooved
copper pipe & hydrophilic aluminum fin coil
Fan power
KW
0.7
1.5
Air volume
m³/h
127
0
0
127
0
0×2
Fan type
Axial flow fan
Fan quantity
1
2
Water side heat
exchanger
Type
Plate heat exchanger
Shell & Tube heat exchanger
Rated water flow
m³/h
5.6
12
Inlet/outlet pipe
DN65
R 2"
(external screw thread)
Water dirt coefficient
m2.
℃
/KW
0.018
0.018
Standard pressure
Mpa
1.0
1.0
Water resistance
kPa
40
45
Sound pressure level
1m away
dB(A)
60
65
Sound power level
1m away
dB(A)
76
83
External dimension
Unit length
mm
918
2060
Unit width
mm
1038
780
Unit height
mm
1810
2170
Package
dimension
Unit length
mm
1075
2200
Unit width
mm
940
830
Unit height
mm
1950
2280
Weight
Unit weight
kg
270
630
Gross weight
kg
290
645
Operation weight
kg
280
670
Safety & functional
protections
High/low Pressure Protection,Water Lackage delay Protection, Freeze Protection,Overload &
Overheat Protection, Phase Loss, Phase Sequence Protection
Note:
1. Nominal refrigerating condition: water outlet temperature is 7°C, ambient temperature is 35°C, and water flow is 0.172[m3/
(h·kW)].
2. Nominal heating condition: water outlet temperature is 45°C, ambient temperature is 7°C for dry bulb and 6°C for wet bulb,
and water flow is listed in the above table.
3. Unit operating range: conforming to GB/T 18430.1& GB/T 18430.2.
4. Scaling factor of circulating water: 0.018m2·°C/kW.
5. The specifications in the table may vary with changes in product design without prior notice.
Model
3.
Specification
Summary of Contents for CA0035EAND
Page 1: ...1 Service Manual AIR COOLED MODULAR CHILLER SYJS 05 2021 B Edition 2021 05 ...
Page 10: ...8 4 Dimension CA0035EAND 6 Unit Base Diagram ...
Page 12: ...10 CA0100EAND CA0130EAND 7 Unit Base Diagram 5 2 8 1 0 5 5 1 1320 0 7 1 2 ...
Page 37: ...35 8 Wiring Diagram ...
Page 38: ...36 ...
Page 39: ...37 ...
Page 40: ...38 ...