5. Connection of Communication Wires
Handest
Master unit of
modular
Slave unit of
modular 1
Slave unit of
modular 2
Slave unit of
modular N
2
+12V
Output wiring terminal
Output wiring terminal
Isolating wires ground
Output wiring terminal
Output wiring terminal
+12V
+12V
+12V
+12V
GND
GND
GND
GND
GND
A1
A1
A1
A1
A1
B1
B1
B1
B1
B1
Red
Red
Red
Red
Blue
Blue
Blue
Blue
Yellow
Yellow
Yellow
Yellow
Green
Green
Green
Green
RS485-A
RS485-A
RS485-A
RS485-A
CN19
CN19
CN19
CN19
Conductir
(Tinned cooper wire, twisted, with
the cross-sectional area at least
0.5mm² or 20AWG)
Shielding layer
(Tinned cooper wire, twisted
or braided, witn the shielding
ratio at least above 95%)
Insulator
Outer sheath (PVC)
Description:
1. The network connecting wires with compact shielding layer and small lay of twisted conductors shall be selected
to the greatest extent.
2. Refer to UL2547 or UL2791 wire standards.
3. The length of control wire shall not exceed 1000 m.
4. The control wire routing must be more than 200 mm away from the heavy-current installations.
4. Requirements for Communication Wires
6. Address Code Setting
The former four digits of the eight-digit code switch are for module address setting, and the latter four for unit mode
and capacity setting. The unit mode and capacity codes have been set in delivery, and they are unchangeable.
The unit address codes default to ON, ON, ON and ON (for master unit), and in delivery, the codes default to 0N,
0N, 0N and 0N.
The former four digits are available for module address:
Address No. SW1 SW2
SW3
SW4
0
ON
ON
ON
ON
1
ON
ON
ON
OFF
2
ON
ON
OFF
ON
3
ON
ON
OFF
OFF
4
ON OFF
ON
ON
5
ON OFF
ON
OFF
6
ON OFF
OFF
ON
7
ON OFF
OFF
OFF
8
OFF ON
ON
ON
Address No.
SW1
SW2
SW3
SW4
9
OFF
ON
ON
OFF
10
OFF
ON
OFF
ON
11
OFF
ON
OFF
OFF
12
OFF
OFF
ON
ON
13
OFF
OFF
ON
OFF
14
OFF
OFF
OFF
ON
15
OFF
OFF
OFF
OFF
Note:
(1) There is no same address code in one system.
(2) The above address codes must be set by professionals.
Summary of Contents for CA0035EAND
Page 1: ...1 Service Manual AIR COOLED MODULAR CHILLER SYJS 05 2021 B Edition 2021 05 ...
Page 10: ...8 4 Dimension CA0035EAND 6 Unit Base Diagram ...
Page 12: ...10 CA0100EAND CA0130EAND 7 Unit Base Diagram 5 2 8 1 0 5 5 1 1320 0 7 1 2 ...
Page 37: ...35 8 Wiring Diagram ...
Page 38: ...36 ...
Page 39: ...37 ...
Page 40: ...38 ...