Inspection and maintenance
Minimum inspection/maintenance measures
Technical changes reserved
119
8.2
Minimum inspection/maintenance measures
The minimum maintenance conditions for switchgear and controlgear assemblies
with FWU distribution enclosures are listed below (compliance based on
VDE 0100, Part 610 for switchgear assemblies):
The recurring tests during commissioning, in the event of changes, after faults or
at suitable intervals include:
-
Inspections
-
Measurements
-
Testing
-
Documenting test results
-
Eliminating the identified defects, for example, by replacing the faulty
operating equipment or devices
-
Documenting the performed work and changes.
Tests through inspection
In the inspection, the electrically skilled person checks the electrical switchgear
for perfect working order, including its operating equipment and devices. The
inspection includes both the equipment exterior/environment and the internal
fittings.
➢
Check the protection against the direct and indirect contact of active
parts.
➢
Check the basic protection and the basic insulation.
➢
Check the additional insulation for fault protection.
➢
Check all necessary covers for personal protection.
➢
Check for signs of ageing.
➢
Check for mechanical, chemical, electrical and thermal stress.
External inspections, tests
Test values, comments, remedy
Test the ambient conditions
-
Effectiveness of the ventilation system and
heating of operating space
-
Room temperature, relative humidity, aggres-
sive air components, dust
Accessibility, minimum distances
Escape routes, clearances
Visual inspection of covers and jacket-
ings
Damage that adversely affect the type of protec-
tion, such as:
-
Missing parts
-
Locking of doors
-
Paintwork damage
Inspections
Remarks
Condition of jacketing, attachment,
cover
Repair if necessary, replace housing parts, clean
soiling and fix the fastenings, observing the in-
stallation manuals in doing so
Check for corrosion traces
-
Repair damage with a suitable
FZ791N
touch-up stick. For more significant damage,
grind, clean (e.g. with white spirit,
spot-removing spirit or universal thinner) and
then paint
-
Check the operating conditions and ambient
conditions
Ventilation/traces of a rise in tempera-
ture
Ensure clearance in front of ventilation inserts,
take suitable measures
Hinge pin lock
Lock, replace missing hinge pins