![background image](http://html1.mh-extra.com/html/hager/hic4-a-series/hic4-a-series_instruction-manual_3234219020.webp)
6LE007621A
20
10.2.
Auxiliary contact operating schedule
Position I
Position 0
Position II
C.A. Position I
C.A. Position 0
C.A. Position II
11-14 Closed
11-12 Open
01-04 Closed
01-02 Open
21-24 Closed
21-22 Open
Position I
Position 0
Position II
C.A. Position I
C.A. Position 0
C.A. Position II
11.
Operation
11.1.
Presentation of the product interface
11.1.1. Product interface
1. Source I and Source II availability
indicators
2. Fault LED
3. Auto LED
4. Dip switchs
5. Adjustment potentiometers of the rated
voltage and frequency and voltage
thresholds
6. Potentiometers to set timers
6
6
5
5
3
2
4
1
1
2
5
3
4
1. Locking
• Option to padlock using a 1 x 8 mm max. padlock.
2. AUT/MAN cover
• Open the cover to switch to manual mode.
• Close the cover to return to automatic (remote control) mode.
• Open and close the cover to clear faults.
3. Auto/Manual mode sensor
4. Switch position indicators
• Display of position I, 0, II.
5. Manual switching
• Insert the Allen key (5.0 mm) provided and turn to switch
manually.
• Manual operation is not possible when padlocked.