![background image](http://html1.mh-extra.com/html/hager/hic4-a-series/hic4-a-series_instruction-manual_3234219019.webp)
6LE007621A
19
10.1.
Terminal connectors designation
Type
Terminal no.
Application
Status
of the
contact
Description
Output
characteristics
Recommended
connection cross-
section
Inputs
I1: 207 / 208 Network-Network
With priority
Dry potential free
contact
0.5 to 2.5 mm²
(rigid)
0.5 to 1.5 mm²
(stranded)
Without priority
Network-Genset
Automatic retransfer
Manual retransfer
I2: 207 / 209 Network-Network
Source priority I
Dry potential free
contact
Source priority II
Network-Genset
Stop the test on load
Test on load
I3: 207 / 210 Network-Network
or
Network-Genset
AUTO mode
Dry potential free
contact
Automatic mode inhibition
Outputs
O1: 63 / 64
Network-Network
or
Network-Genset
Product not available :
- Manual mode
- Operation failure
- Electronic failure
- No power sources
Resistive load
2A 30 VDC
0.5A 230 VAC
Pmax : 60W
or 125 VA
Umax : 30 VDC
or 230 VAC
Product available
O2: 73 / 74
Network-Genset
No start command genset
Resistive load
2A 30 VDC
0.5A 230 VAC
Pmax : 60W
or 125 VA
Umax : 30 VDC
or 230 VAC
Generating set starting
Type
Terminal no.
Status of
the contact
Description
Output
characteristics
Recommended
connection cross-
section
Auxiliary
contact
block
HZI300
11/12/14
11
14
12
Changeover switch in position I
250 VAC 5A AC1
30 VDC 5A
250 VAC 2A AC13
0.5 to 2.5 mm²
(rigid)
0.5 to 1.5 mm²
(stranded)
21/22/24
21
24
22
Changeover switch in position II
250 VAC 5A AC1
30 VDC 5A
250 VAC 2A AC13
01/02/04
01
04
02
Changeover switch in position 0
250 VAC 5A AC1
30 VDC 5A
250 VAC 2A AC13