13. Troubleshooting guide

Symptoms

Action to be carried out

Expected results

1

Product is off, no 

LED is lit

Check for a voltage of 176 to 288 VAC on the supply terminals:

- Terminals 1-7 correspond to SOURCE I

- Terminals 1-7 correspond to SOURCE II

The "AUT" LED is lit (if the cover is 

closed)

2

The "Priority 

SOURCE 

Availability" LED 

does not come on

Check the following parameters:

• the type of network =>  3P (DIP Switch 1 on position A) 

1P (DIP Switch 1 on position B)

• frequency  

=>  50 Hz (DIP Switch 2 on position C) 

60 Hz (DIP Switch 2 on position D)

• the nominal voltage => with a multimeter, measure the voltage across the terminals and report the value on the 

potentiometer

The "Priority SOURCE Availability" 

LED is lit

Check the thresholds and hysteresis of rated voltages (∆U) and frequencies (∆F) and report them on the 

corresponding potentiometer

If using an Auto transformer - proceed as follows upon 1st switching on

• Step 1:  HIC4xxA must be connected to a three-phase + neutral network (4NBL) for setting the neutral position. 

Neutral position is detected upon first switching on

• Step 2:  Connect the autotransformers. Warning: Neutral must be connected on the same side as in step 1

How to reset the neutral position:

• Step 1: Open the cover

• Step 2: Set DIP Switch 1 from 3P to 1P

• Step 3: Set DIP Switch 1 from 1P to 3P

• Step 4: Close the cover

3

The "Emergency 

SOURCE 

Availability" LED 

does not come on

Check the following parameters:

• the type of network  =>  3P (DIP Switch 1 on position A) 

1P (DIP Switch 1 on position B)

• frequency 

=>  50 Hz (DIP Switch 2 on position C) 

60 Hz (DIP Switch 2 on position D)

• the nominal voltage =>  with a multimeter, measure the voltage across the terminals and report the value on the 

potentiometer 

The "Emergency SOURCE 

Availability" LED is lit

CAUTION:

 a generator operating off load can generate a Fr and a U lower than the nominal values:

Check the thresholds and hysteresis of rated voltages (∆U) and frequencies (∆F) and report them on the 

corresponding potentiometer.

If using an Auto transformer - proceed as follows upon 1st switching on 

•  Step 1: HIC4xxA must be connected to a three-phase + neutral network (4NBL) for setting the neutral position. 

Neutral position is detected upon first switching on.

• 

 Step 2: Connect the autotransformers. Warning: Neutral must be connected on the same side as in step 1

How to reset the neutral position:

• Step 1: Open the cover

• Step 2: Set DIP Switch 1 from 3P to 1P

• Step 3: Set DIP Switch 1 from 1P to 3P

• Step 4: Close the cover

4

The product 

remains switched 

off after the 

Priority SOURCE 

is lost

Check if voltage is between 176 to 288 VAC across the power supply terminals of emergency SOURCE:

- Terminals 1-7 correspond to the Emergency Source

The "AUT" LED is lit

In case of transformer/ Genset, check that FT timer (Main Failure Timer) has finished counting down.

• Use a stopwatch.

• Start the stopwatch when the product has lost its Priority SOURCE.

- Contact 73 - 74 must be closed after 60 s max (M-G application)

- GENSET run command = contact 73-74 closed

- GENSET stop command = contact 73-74 open

The Genset works and the LED 

"Emergency Source Disponibility" 

is lit

5

The product does 

not switch over 

after the Priority 

SOURCE is lost

Check that the product is not in manual mode:

• Automatic mode = cover closed

• Manual mode = cover open

The "AUT" LED is lit

Check that automatic operation has not been inhibited by an external order (terminals 207-210).

Check the status of led « Emergency SOURCE availability ». If it is off, refer to the symptom concerned (higher in the 

list) 

The "AUT" and "Emergency 

SOURCE Availability" LEDs are lit

In case of Transformer / Transformer, check the setting of FT timer (Main Failure Timer). The duration of this time 

delay is between 0 and 60 s. If necessary, use a stopwatch to check switching to SOURCE after FT countdown

At the end of the time delay, the 

product switches to mechanical 

position 0, and to emergency 

SOURCE

6

The product does 

not switch over 

when the Priority 

SOURCE is 

restored

Check that the product is not in manual mode:

• Automatic mode = cover closed

• Manual mode = cover open

The "AUT" LED is lit

Check that automatic operation has not been inhibited by an external order (terminals 207-210).

Check the state of the "Priority Source Availability" LED. If it is off, refer to the symptom concerned (higher in the list)

The "AUT" and "Emergency 

SOURCE Availability" LEDs are lit

Check the setting of RT timer (Main Return Timer). The duration of this delay is between 0 and 30 min. Use a 

stopwatch to check the switch to Priority SOURCE after the RT timer

At the end of the time delay, the 

product switches to mechanical 

position 0, and to priority SOURCE

Check that the "manual retransfer" function is not active*

• Retransfer mode activated = contact 207-208 closed

• Retransfer mode desactivated = contact 207-208 open

 

* if this function is not required

Contact 207-208 must be open to 

enable switching to priority SOURCE

7

Return to Priority 

SOURCE 

has been 

executed, but 

the Emergency 

Source (for 

a Generator) 

continues to 

operate

Check CDT timer (Cool Down Timer) has finished counting down - Fixed time delay: 4 min

• Use a stopwatch.

- Start the stopwatch when the product has switched over to the Priority SOURCE.

- Contact 73-74 must be open after time delay CDT has finished counting down

The GenSet switches off and led " 

Emergency SOURCE availability" 

is OFF”

Check that the product is not in automatic mode:

• Automatic mode = cover closed

• Manual mode = cover open

The "AUT" LED is lit

Check that automatic operation has not been inhibited by an external order (terminals 207-210).

Hager Electro S.A.S., Boulevard d'Europe, B.P. 3, 67215 OBERNAI CEDEX, France - www.hager.com

Hager 01.21 - OCOM 140736

Summary of Contents for HIC4 A Series

Page 1: ...6LE007621A z Automatic Transfer Switching Equipment Instruction manual HIC4xxA 6LE007621A 1...

Page 2: ...optional accessories 12 8 1 Auxilliary contacts 12 8 2 Voltage sensing and power supply tap 12 8 3 Bridging bars 4P 13 8 4 Terminal shrouds 13 8 5 Sealable cover 13 9 Connection of the power circuits...

Page 3: ...5 1 Single phase version 22 11 5 2 Three phase version 23 11 6 Sealable configuration cover 24 11 7 Automatic mode 24 11 7 1 Sealable Auto Manual cover 24 11 8 Possible actions 24 11 9 Manual Automat...

Page 4: ...opean Directives governing this type of product and includes CE marking on each product No covers other than that for auto manu on the HIC4xxA should be opened with or without voltage as there may sti...

Page 5: ...ety between a normal and an alternate source A complete product delivered as a fully assembled and tested solution Intuitive HMI for emergency local operation Integrated and robust switch disconnectio...

Page 6: ...II Monitoring 3 voltages on networks I and II Frequency on networks I and II Automatic controller configuration By potentiometer and micro switch Vn Fn V threshold F threshold Driving with or without...

Page 7: ...switch with the motorisation on the right hand side as shown 3 2 Specifications and advantages 1 Power section A fully integrated and interlocked transfer switch with high electrical performance offe...

Page 8: ...0 Bridging bars To provide a common point on the outgoing side of the switch load side Three phase product Rating 125A HZI400 Rating 160A HZI401 Terminal shrouds Protection against direct contacts wit...

Page 9: ...N fuses Fuse protected short circuit withstand kA eff 50 50 50 50 50 50 40 Associated fuses gG DIN 20 40 63 80 100 125 160 Short circuit capacity Rated short term withstand current Icw 1s kA eff 4 4 4...

Page 10: ...de rating 40 C t 70 C with de rating see Technical Characteristics Altitude Max 2000 m without de rating Correction factors 2 000 m A 3 000 m 3 000 m A 4 000 m Ue 0 95 0 80 Ie 0 85 0 85 Storage 1 year...

Page 11: ...25 Nm 2 X Posidriv PZ2 OK OK STEP 1 STEP 2 STEP 3 STEP 4 Posidriv PZ2 Posidriv PZ2 2 2 lb in 0 25 Nm 2 X Posidriv PZ2 OK OK STEP 1 STEP 2 STEP 3 STEP 4 Posidriv PZ2 Posidriv PZ2 2 2 lb in 0 25 Nm 2 X...

Page 12: ...install use the screws supplied with the module Pozidriv PZ2 1 Nm Use 20mm screws for 1 module Use 35mm screws for 2 modules 0 5 to 2 5 mm solid stranded 0 5 to 1 5 mm 10 mm PUSH IN 8 2 Voltage sensin...

Page 13: ...l Metric Allen size 4 5 0 Nm Allen size 4 Hexagonal Metric 44 1 lb in 5 0 Nm 15 mm 0 59 8 to 00 AWG 10 to 70 mm2 6 to 70 mm2 10 to 00 AWG X8 Allen size 4 Hexagonal Metric 44 1 lb in 5 0 Nm 15 mm 0 59...

Page 14: ...00 A 125 A 160 A Min cable size recommended mm2 10 10 16 25 35 50 50 Max cable size recommended mm2 50 50 50 50 50 70 70 With extension unit Not compatible with aluminium cables 9 2 Parallel pole set...

Page 15: ...Vdc 1A 125Vac 0 5A 230Vac resistive max 60W or 250VA START STOP OK NOK 2 4 6 8 1 3 5 7 2 4 6 8 1 3 5 7 2 4 6 8 1 3 5 7 2 4 6 8 1 3 5 7 AUT 250VAC 5A AC1 30VDC 5A DC1 12 14 11 21 24 22 01 04 02 OK OK O...

Page 16: ...ingly The example below shows the wiring for a product configured with neutral on the left A new product must have the neutral configuration pre programmed as on the left or on the right at the first...

Page 17: ...L1 L1 N N L1 L1 N TEST PRIORITY AUT 63 64 73 74 207208209210 63 64 73 74 2A 30Vdc 1A 125Vac 0 5A 230Vac resistive max 60W or 250VA 2A 30Vdc 1A 125Vac 0 5A 230Vac resistive max 60W or 250VA START STOP...

Page 18: ...21 11 14 12 01 04 02 250VAC 5A AC1 30VDC 5A DC1 22 24 21 11 14 12 01 04 02 250VAC 5A AC1 30VDC 5A DC1 22 24 21 11 14 12 01 04 02 HZI300 250VAC 5A AC1 30VDC 5A DC1 22 24 21 11 14 12 01 04 02 250VAC 5A...

Page 19: ...etwork Network or Network Genset Product not available Manual mode Operation failure Electronic failure No power sources Resistive load 2A 30 VDC 0 5A 230 VAC Pmax 60W or 125 VA Umax 30 VDC or 230 VAC...

Page 20: ...ators 2 Fault LED 3 Auto LED 4 Dip switchs 5 Adjustment potentiometers of the rated voltage and frequency and voltage thresholds 6 Potentiometers to set timers 6 6 5 5 3 2 4 1 1 2 5 3 4 1 Locking Opti...

Page 21: ...over switching Manual DIP switch programmation MANUAL MODE 11 3 Manual switching Use the handle situated on the front panel under the cover to manoeuvre the changeover switch To simplify the operation...

Page 22: ...y contact module comprises one NO NC changeover contact for each position I O II To install use the long screws supplied with the module 4 5 6A 6B 6C Max 8 Nm Extension To simplify operation use the h...

Page 23: ...in position O An auxiliary contact module comprises one NO NC changeover contact for each position I O II To install use the long screws supplied with the module 4 5 6A 6B 6C Max 8 Nm Extension To si...

Page 24: ...that the changeover switch is in automatic mode AUT LED lit 11 7 1 Sealable Auto Manual cover Auto Manu mode can be protected by sealing the standard Auto Manu cover as shown 11 8 Possible actions Onc...

Page 25: ...r reserves Mode settings G H 207 208 207 208 MODE 1 MODE 3 MODE 2 MODE 4 AUT Priority MODE AUT Priority 11 9 1 Mode 1 Automatic retransfer Network Genset applications Contact 207 208 open automatic re...

Page 26: ...on Source 1 available Product in position I Contact 207 208 open Contact 207 209 open Genset start order Genset available Transfer I II Transfer II I Genset stop Return of source 1 Loss of source 1 Lo...

Page 27: ...min 5 sec 5 sec RT 5 sec FT 207 208 207 208 NORMAL PRIORITY II TEST Transfer from I to II Product in position I Source available Source missing Timer is counting down Genset available Genset missing T...

Page 28: ...ble Product in position I Contact 207 208 closed Contact 207 209 open Genset start Transfer I II Transfer II I Genset stop Return of source 1 Opening of contact 207 208 Loss of genset End of FT End of...

Page 29: ...enset Source 1 available Product in position I Contact 207 208 open or closed Contact 207 209 open Transfer I II Loss of genset Opening of contact 207 209 Transfer II I Genset stop End of CDT Genset s...

Page 30: ...09 207 209 TEST PRIORITY PRIORITY TEST 5 sec 5 sec RT FT FT RT Transfer from I to II Product in position I Source available Source missing Timer is counting down NORMAL PRIORITY II TEST Yes Yes Loss o...

Page 31: ...ces 1 and 2 available Product in position I Contact 207 208 open Contact 207 209 open Transfer I II Opening of contact 207 209 Closing of contact 207 209 Priority source 2 Transfer II I Transfer II I...

Page 32: ...is counting down 207 209 207 209 TEST TEST 5 sec 5 sec FT FT ou ou Transfer from I to II Product in position I Source available Source missing Timer is counting down NORMAL PRIORITY II TEST Yes Loss o...

Page 33: ...rk application Sources 1 and 2 available Product in position I Contact 207 208 closed Contact 207 209 open Transfer I II Impulsion of contact 207 209 Impulsion of contact 207 209 Transfer II I Return...

Page 34: ...ritical level and application where the product is installed should form an essential and integral part of the maintenance plan Good engineering practice is imperative whilst all necessary precautions...

Page 35: ...of transformer Genset check that FT timer Main Failure Timer has finished counting down Use a stopwatch Start the stopwatch when the product has lost its Priority SOURCE Contact 73 74 must be closed a...