I-LS02111
www.hagerco.com
6
Rev 1, 5/16
NOTE: Once the initial RTC has been set, you can change the RTC time after the lock
has been setup. Follow the code sequence below.
[
*
] [Master code] [
*
] [50] [
*
] [YYMMDDhhmmss] [
*
]
WARNING! When the RTC is changed, the Passage Mode Active Period and
all Service Codes will be reset.
3.1.4.
Reset to Factory Default Settings
Soft Reset- All setting values will return to factory default, except Master Code and
event logs.
Use the code below to Reset:
[
*
] [Master code] [
*
] [00] [
*
] [29] [
*
]
If the setting is successful, then the buzzer will beep once with a green light. If the
setting fails, then the buzzer will beep three times with a blinking red light.
The setting sequence will be exited if the idle time is more than 20 seconds, or [#] is
pressed to exit immediately.
Hard Reset-All values will return to factory default and the event logs will be deleted.
Follow the steps below to reset the unit:
1.
Remove the battery cover.
2.
Turn off the POWER SWITCH (refer to section 3.2.1).
3.
Press and Hold the RESET button (refer to section 3.2.2).
4.
Turn on the POWER SWITCH and wait for 12 seconds.
5.
After Buzzer beeps once with a green light, release the RESET button.
3.1.5.
Setting Re-lock Delay Time
Use the code below to set the Re-locking Delay Time:
[
*
] [Master or Manager code] [
*
] [00] [
*
] [05] [
*
] [SS] [
*
]
If the setting is successful, then the buzzer will beep once with a green light. If the
setting fails, then the buzzer will beep three times with a blinking red light.
The setting sequence will be exited if the idle time is more than 20 seconds, or [#] is
pressed to exit immediately.
SS: Re-locking delay time; Range is 00-99 seconds; DEFAULT is 5 seconds
SS=00 will deactivate the re-lock function
NOTE:
The setting will fail if the RESET button is released during step 4. If this
happens, repeat steps 2 through 5.