Single zone AOV User Manual
PANEL CONTROLS & INDICATIONS
39
Approved Document Ref: UI-SZAOV-01 Issue 2.01
DISABLE MODE
Disable Mode is used to disable or isolate individual circuits.
To initialise Disable Mode, firstly activate the controls by turning the key switch or by
entering the four-digit code. Then press and hold the Disable Mode button (1) for 3 seconds.
After 3 seconds the panel will bleep and the General Disablement LED and Input LED will
pulse slowly, indicating that the Input circuit is in disable selection mode.
Pressing the Disable Mode button again will move the selection to the desired option:
•
Vent (Input LED)
•
Open (Vent Open LED)
•
Close (Vent Closed LED)
•
Detector (Detector LED)
•
Rain (Rain Status LED)
•
PIR (PIR Status LED)
When the desired circuit or output to be disabled is indicated by a slow pulsing LED, use the
ENTER button to select it. Once selected the indicator LED will change to a rapid pulse.
Pressing ENTER again will toggle the circuit between disabled and enabled. Then use the
Disable Mode button again to move to the next circuit. Any or all circuits can be disabled
simultaneously.
When all disablements have been set, press and hold the Disable Mode button for 3
seconds again. This will exit the disable selection mode and the panel will return to standby.
All disabled circuits and the General Disablement will now be indicated by a steady LED.
To enable the circuits again, repeat the above process using the Disable Mode button to
select the circuit and the ENTER button to remove the disablement.