Single zone AOV User Manual
SETUP AND PROGRAMMING
34
Approved Document Ref: UI-SZAOV-01 Issue 2.01
Thermostat Controlled Ventilation Mode
Thermostat Controlled Ventilation Mode
This option allows for thermostat control of vent opening by using a thermostat to switch in a 10K
resistance between the MANUAL OPEN or MANUAL CLOSE and the MANUAL COMMON
terminals. This will allow the vent to open or close to a pre-defined position when the pre-set
temperature on the thermostat is reached.
Enter the above code and press ENTER button.
Press button 1 or button 3 to select which of the options to change:
•
Open Vent to thermostat position (Vent Open LED)
•
Close Vent to thermostat position (Vent Close LED)
Press ENTER button to set the required position of the vent as indicated by the General Fault
LED, Disablement LED, Test Mode LED and Rain Status LED as shown below:
Setting
General Fault
Disablement
Test Mode
Rain Status
Disabled
-
-
-
-
Close
On
-
-
-
10%
-
On
-
-
20%
On
On
-
-
30%
-
-
On
-
40%
On
-
On
-
50%
-
On
On
-
60%
On
On
On
-
70%
-
-
-
On
80%
On
-
-
On
90%
-
On
-
On
Open
On
On
-
On
Repeatedly press button 2 to cycle through the above settings.
Press ENTER to exit the edit mode and select another option.
To finish, press button 1 and hold for about 3 seconds to return to Main Display.