Single zone AOV User Manual
SETUP AND PROGRAMMING
30
Approved Document Ref: UI-SZAOV-01 Issue 2.01
Clear All Disablements
Reset All Disablements.
Enter the required code as above and press the ENTER button.
Then press the ENTER button again and hold for 3 seconds. Any disablements will now be
cleared.
The panel will bleep to acknowledge the reset.
Miscellaneous Program Options
Miscellaneous Program Options
There are five miscellaneous options using code 2-1-2-3. The options are represented by the
‘Vent Open’, ‘Vent Closed’, ‘Input’ & ‘Detector’ LEDs. The options are:
1.
Set motor opening time (Vent Open LED)
2.
Set motor closing time (Vent Closed LED)
3.
Disable actuator short circuit monitoring (Vent Open LED and Vent Closed LED)
4.
Disable
battery monitoring (Input LED)
5.
Disable muted tone beeps (Detector LED)
6.
Set keypad entry code (Input LED and Detector LED)
Enter the above code and press the ENTER button. The Vent Open LED will be on steady. Use
buttons 1 & 3 to move forwards or backwards through the options as per above. With the desired
LEDs lit, press the ENTER button to access edit mode for the chosen option. The LEDs will now
pulse to indicate EDIT mode.
OPTION 1 (Vent Open LED) Set Motor Opening Time
Set the Actuator motor opening time for motorised vents. The time is set in 5 second steps.
The time is represented by the General Fault, General Disablement, Test Mode, Rain status, PIR
Status and Power Supply Fault LEDs using a 6-bit binary code.
With the Vent Open LED pulsing, the other LEDs listed above will show the currently set time
(factory default = 60 seconds). Use buttons 1 & 3 to increase or decrease the time by 5 seconds
at a time. A minimum time of 10 seconds and a maximum time of 300 seconds can be set.
Press the ENTER button to set the time and return to the main menu.
OPTION 2 (Vent Closed LED) Set Motor Closing Time
Set the Actuator motor closing time for motorised vents. The time is set in 5 second steps.
The time is represented by the General Fault, General Disablement, Test Mode, Rain status, PIR
Status and Power Supply Fault LEDs using a 6-bit binary code.
1
1
2
1
2
1
2
3