97
Figure 131 Removing the supercapacitor holder
11.
Install a new power fail safeguard module. For more information, see "
storage controller and a power fail safeguard module
12.
Reconnect the removed cables to the front drives backplane. For more information, see
"
."
13.
Install the removed fan cage. For more information, see "
."
14.
Install the removed air baffles. For more information, see "
15.
Install the access panel. For more information, see "
."
16.
Rack-mount the server. For more information, see "
17.
Connect the power cord. For more information, see "
18.
Power on the server. For more information, see "
Verifying the replacement
Log in to HDM to verify that the flash card and the supercapacitor are in a correct state. For more
information, see HDM online help.
Replacing the power fail safeguard module for a standard
storage controller
CAUTION:
To avoid server errors, do not replace the power fail safeguard module when a drive is performing
RAID migration or rebuilding. The Fault/UID LED is off and the Present/Active LED is flashing green
on a drive if the drive is performing migration or rebuilding.
Procedure
1.
Power off the server. For more information, see "
2.
Remove the server from the rack. For more information, see "
Removing the server from a rack
."
3.
Remove the access panel. For more information, see "
."
4.
Remove the air baffles as needed. For more information, see "
."
5.
Remove the fan cage. For more information, see "
."
6.
Disconnect cables that might hinder the replacement.