[:SOURce]:SIMulation:NORMal<1|2>
:FREQuency
Set
Query
Description
Sets or queries the frequency of the normal1 or
normal2 step of the simulation mode.
Syntax
[:SOURce]:SIMulation:NORMal<1|2>:FREQuency
{<NR2>|MINimum|MAXimum}
Query Syntax
[:SOURce]:SIMulation:NORMal<1|2>:FREQuency?
[MINimum|MAXimum]
Parameter/Return
parameter
<1|2>
Normal 1 or Normal 2
<NR2>
Frequency of abnormal step
MINimum
Minimum frequency
MAXimum
Maximum frequency
Example
:SIM:NORM1:FREQ 60
Sets the frequency to 60Hz.
[:SOURce]:SIMulation:NORMal<1|2>
:PHASe:STARt:ENABle
Set
Query
Description
Enables/Disables the ON Phs parameter of the
normal1 or normal2 step for the Simulation mode.
Syntax
[:SOURce]:SIMulation:NORMal<1|2>:PHASe:STARt:E
NABle {<bool>|OFF|ON}
Query Syntax
[:SOURce]:SIMulation:NORMal<1|2>:PHASe:STARt:E
NABle?
Parameter/Return
parameter
<1|2>
Normal 1 or Normal 2
OFF | 0
Disabled
ON | 1
Enabled
Example
:SIM:NORM1:PHAS:STAR:ENAB 1
Enable the ON Phs.