K-BUS
®
KNX/EIB
Universal Interfaces
49
6.8. Communication object “Shutter control”
The communication object “Shutter Control” will be shown in Fig.6.8
Fig.6.8 Communication object “Shutter control”
No.
Function
Object name
Data type
Flags
DPT
1
CH X shutter UP/DOWN
Output shutter UP/DOWN, X 1Bit
C,T
1.008 up/down
This communication object move up/down the shutter by sending command by bus. It will move down if the
communication object send a “1” telegram, it will move up if sending a “0”.
2
CH X Stop/adjust adj
Output Stop/adjust adj, X
1Bit
C,T
1.007 step
It will stop/adjust the shutter by sending command by bus. It will stop/ adjust down if sending a “1” telegram, and it will
stop/adjust up if sending “0”.
3
CH X Upper limit position
Upper limit position, X
1Bit
C,W
1.003 enable
It is used to limit the upper moving. It is limit the upper moving if the object receive a logic value “1”, and negate it if
receive “0”.
4
CH X Lower limit position
Lower limit position, X
1Bit
C,W
1.003 enable
It is used to limit the lower moving. It is limit the lower moving if the object receive a logic value “1”, and negate it if
receive “0”.
Form 8 Communication object “Shutter control”
6.9. Communication object “LED X-flashing”
The communication object “LED X—Flashing” will be shown in Fig.6.9.
Fig.6.9 Communication object “LED X-Flashing”
No.
Function
Object name
Data type
Flags
DPT
28
LED X Flashing
LED. Flashing, X
1Bit
C,W
1.001 switch
It is used to control the LED flashing. It will start flashing if receive “1” or “0” telegram (defines by “LED flashing, if”), the
flashing time set by parameter. And it will stop LED if receive “0” or “1”.
29
LED X Permanent on
LED permanent on, X
1Bit
C,W
1.001 switch
It is used to open LED for a long period and its priority is higher than the communication object “LED. Flashing, X”. It
will open LED if receive telegram “1”, negate priority and the LED resume the foregoing operation if receive “0”.
30
LED X Send its status
Send its status, X
1Bit
C,T
1.001 switch
It is visible if “Send status by object “Tele. Status”” selected “Yes”
,
it is used to send the status of LED. Sending “1”
means LED open or flashing, and sending “0” means the LED is stop. The object LED. Flashing, X” will send telegram “1” if
sending open flashing requirement every time.
Form 9 Communication object “LED X-Flashing”