K-BUS
®
KNX/EIB
Universal Interfaces
31
Toggle
The current object value is inverted in the “Toggle” setting.
Parameter “Value on every operation send”
This parameter defines whether to send the operation value.Options:
No
Yes
If “yes” is entered in this parameter, the associated object value is updated and sent after each
operation in the case of multiple push button actions. Example: For three-fold operations, the objects
“output 1-fold” (after the first operation), “output 2-fold” (after the second operation) and “output 3-fold”
(after the third operation) are sent. If “No” is selected, the current value will be send on the bus until the
last operation delay (the delay time is the interval time between two operations).
Parameter “Max. time between two operation”
This parameter sets the interval between two operations. If there are no further operations within
this period, the object “output 1-fold” is sent again.Options:
0.3s
0.5s
…
10s
Parameter “Additional object for long operation”
This parameter defines whether to activate the long operation. If a long operation is carried out after
one or several short operations within the maximum period, the short operations are ignored.Options:
No
Yes
Parameter “Long operation after”
This parameter is visible if long operation activate. The period is defined here, after which an
operation is interpreted as “long”.Options:
0.3s
0.5s
…
10s