K-BUS
®
KNX/EIB
Universal Interfaces
47
6
CH X level increment/
decrement
level increment/
decrement, X
1bit
C,W
1.007 step
The communication object “level increment/decrement, X” is used to increase/decrease the level of the switch. It will
increase one level when sending “1” and decrease a level when sending “0”. The detail process will be describe in the
switching sequence parameter chapter.
Form 5 Communication object “Switching sequence”
6.6. Communication object “Counter”
The communication object “Counter” will be shown in Fig.6.6. Including standard counter and
differential counter communication object, both these communication objects are initiated counter by one
operation and the counter range are the same, but the counting are independent of each other.
Fig.6.6 Communication object “Counter”
No.
Function
Object name
Data type
Flags
DPT
1
CH X Counter value
Output counter value
1byte, X
(
1byte/2byte/4byte
)
1byte
2byte
4byte
C,W,T
5.010 counter pulses(0..255)
8.001 pulses difference
7.001 pulses
13.001 counter pulses(signed)
This communication object is used to transmit the current counting value of the standard counter, and it can modify the
counting value simultaneously. Different data type makes the different counting range, it is defines by parameter “Date
width of counter”.
2
CH X Differential
Counter
Differential Counter
1byte, X
(
1byte/2byte/4byte
)
1byte
2byte
4byte
C,W,T
5.010 counter pulses(0..255)
8.001 pulses difference
7.001 pulses
13.001 counter pulses(signed)
It is visible if enable the parameter “Enable differential counter”. This communication object is used to transmit the
current counting value of the differential counter, and it can modify the counting value simultaneously. Different data type
makes the different counting range, it is defines by parameter “Date width of counter”.
3
CH X Request
Counter value
Request
Counter value, X
1Bit
C,W
1.003 enable
This communication object is used to ask for the current counting value of the standard counter and the differential
counter. The communication object “CH X Counter value” and “CH X Differential Counter” will transmit the current counting
value if receive a logic value “1”, it will no reaction if receive a logic value “0” telegram.