K-BUS
○
R
KNX/EIB
Switch Blind Actuator
42
www.video-star.com.cn
Tel.
:(
8620
)
39338986
Fax
:(
8620
)
39338465
3
Output X
Switch status
1bit
C,R,T
1.001 DPT_Switch
This object indicates the contact status (details will be defined by parameter “Object value of switch status:” in “Channel X
1,2
:
Switch”).
If selecting “respond, after read only”, the status telegram will not be sent out until receiving a read request telegrams from the bus
via the object.
If selecting “respond after change”, it will send the status automatically via the object when there are any changes on the output.
If selecting
“
respond always
”
The object will not send current status to the bus, until the device received the request of reading the
switch status from the other bus device operation or the bus.
4
Output X
Enable time function
1bit
C,W
1.003 DPT_Enable
This object will be enabled only when enabling the time function, it can be used to enable and disable the time function. It will
enable the timing function when receiving the value “1”; will disable it when receiving “0”. The operation before disabled it is still
carried out completely. Enable is a default setting after bus voltage recovery if the time function is set.
5
Output X
Delay function
1bit
C,W
1.001 DPT_Switch
When select “delay ” in the parameter “Type of time function”, the object will be activated, then the delay switch function will be
activated via the object.